Appendix C
Troubleshooting and Common Questions
C-2
ni.com
VCR_FULL_ERROR
Delete the card from the Interface Configuration utility, then reinstall.
NIFB Problems
When using the PCMCIA-FBUS card with Windows 2000/NT, Nifb
returns an error message stating that the board cannot be found.
•
Verify the base address and IRQ settings as described in the
•
Select
Start»Programs»National Instruments FBUS»Interface
Config
. Make sure your card appears under the list of interfaces.
•
Make sure the kernel-mode driver is started. To start the driver, select
Start»Settings»Control Panel»Devices»Nifb
. Click the
Start
button.
To avoid manual startup in the future, click
Startup
and select
Automatic
.
When a Fieldbus device is connected to the bus, the NIFB process
often hangs when the title bar reads
Waiting for Startup
Completion
. If I disconnect the cables, it starts fine.
This is probably due to a device address conflict. In the NI-FBUS Interface
Configuration utility, make sure that the interface is not at the same address
as anything else on the link. You also can temporarily give the interface
a visitor address to troubleshoot this problem.
The NIFB process hangs, does not start up, or never shows that it is
running.
•
The card’s base memory address conflicts with another device. Try
using a different base memory address. Windows does not always
detect all conflicts. Even if Windows reports no conflicts, trying
a different address after you have eliminated the IRQ or Fieldbus
network address often will resolve the problem. You must restart
the machine each time you change base address and/or IRQ.
•
The card’s IRQ conflicts with another device. Try setting the card to
polled mode.
•
The Fieldbus network address is not unique. Remove the cable from
the card. Restart the NIFB process. If it runs successfully, there is
probably a Fieldbus network address conflict. If you have FP-3000
network modules on the bank, powering them off and then back on will
cause them to look on the bus for available addresses and change