Appendix A
Specifications
NI PS-16 Power Supply User Manual
A-14
ni.com
Note
In case of a protection event, audible noise may occur.
Safety
This product is designed to meet the requirements of the following
standards of safety for industrial control and information technology
equipment:
•
IEC/EN 60950-1, UL 508
Note
For UL and other safety certifications, refer to the product label or the
Online
Product Certification
section.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for industrial control and information technology
equipment:
Over-temperature
protection
Yes
Output shut-down with automatic restart
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
T6.3A H.B.C.
Not user replaceable
EMC Immunity
EN 61000-6-2
EN 61000-6-1
Generic standards
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8 kV
15 kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz–1 GHz
10 V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
4 kV
2 kV
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L
→
N
N/L
→
PE
2 kV
4 kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+
→
–
+/–
→
PE
500 V
500 V
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0.15–80 MHz
10 V
Criterion A