Figure 19. PXIe-1086DC Power Drawer
2
1
3
2
1
4
1. Captive Screw
2. Power Drawer Lever
3. Side Latch
4. Power Supply
Caution
If you are using the PXIe-1086DC and SC Express modules with front
mounting terminal blocks together, you must remove the SC Express module front
mount terminal blocks to access the power drawer. Refer to your module
documentation for more information about removing the terminal blocks.
Complete the following steps to remove the power drawer:
Caution
You must disconnect AC or DC power before removing the power
drawer.
1.
Disconnect AC or DC power by pressing the release button on the power cord.
2.
Loosen the drawer lever captive screws with a flat-blade screwdriver until the threads
disengage from the chassis frame.
3.
Rotate the drawer levers to eject the drawer from the chassis frame.
4.
Pull the drawer about halfway out until the side latches engage.
5.
Press in the side latches on both sides to release the drawer and continue to pull out the
drawer.
Caution
Before handling the power supply, allow the fan to stop spinning.
6.
Place the drawer on a table surface to remove the power supply.
7.
Disengage the two screws on the rear of the power supply with a flat-blade screwdriver.
Refer to
for the location of the screws.
8.
Extend the collapsible handle and pull the power supply out of the chassis. Refer to
for the location of the handle.
PXIe-1086DC User Manual and Specifications
|
© National Instruments
|
31