RMX-10050/10051 User Guide
|
© National Instruments
|
5
Operation
1.
Connect load equipment, making sure to observe the outlet ratings.
2.
Turn on the main circuit breaker for the PDU.
3.
Confirm that the main power indicator shows power is present.
Optional Features
Sequencing
The optional sequencing feature is used to support sequential power-up of the outlets. With this
feature, the sequenced start up begins when the remote EPO interface is used to enable the
PDU outputs. The specific start up sequence is defined in the following table.
DC Output
The optional DC output feature provides four independent DC outputs via terminal blocks on the
rear panel. The total DC output is always limited to 500 W. This is divided evenly as 125 W per
each of the four output channels.
The ratings table in this manual describes the specific outputs and ratings for all models except
the RMX-10050 (785342-01). The DC output feature also includes a DC inhibit connector
which can be used to individually control each DC output channel. The connector mounted on
the rear of the PDU is Molex 39-01-2126, and the mating connector is Molex 39-01-2125.
The following table shows the DC Inhibit Connector Pinout.
Table 6.
Sequencing Behavior
Model
Step
Timing
Outlets Controlled
RMX-10050 (785341-01)
1
Immediate
Group A, DC Outputs
2
After two seconds
Group B
RMX-10051 (785344-01)
1
Immediate
J1, DC Outputs
2
After two seconds
J2, J3
RMX-10051 (785343-01)
1
Immediate
J1, DC Outputs
2
After two seconds
J2, J3