6
|
ni.com
|
RMX-10050/10051 User Guide
Remote-EPO
The optional Remote-EPO feature allows external control of all outlets. The toggle switch on the
front panel selects the Remote-EPO mode.
•
OFF
will prevent all outlets from being powered.
•
LOCAL/ON
will enable power to all outlets, unless they are being disabled by the outlet
control bus.
•
REMOTE
will place all outlets under the control of the outlet control bus. The outlet
control bus includes three 3-pin connectors which are wired in parallel. This arrangement
allows multiple PDUs to be connected in a daisy-chain configuration and controlled from
a single control panel. The connectors mounted on the PDU are Amp/TE 1-480304-0, and
the mating connector is Amp/TE 1-480305-0. The 3-pin connectors use two low-voltage
signals as follows:
–
Shorting the ENABLE pin to the RETURN pin with a dry contact will trigger the
Enable signal.
–
Opening the DISABLE pin from the RETURN pin will trigger the Disable signal.
This signal is intended to be operated from a normally-closed contact on a control
switch. Note that the DISABLE pin must be shorted to the RETURN pin to allow the
switched outlets to operate, regardless of the toggle switch positions noted above.
–
Note that the Disable signal has priority, so that if both signals are triggered at the same
time, the net result will be Disable.
Table 7.
DC Inhibit Connector Pinout
Pin
Name
Description
1
PG1
Power Good Channel 1
2
INH1
Inhibit Channel 1
3
PG2
Power Good Channel 2
4
INH2
Inhibit Channel 2
5
PG3
Power Good Channel 3
6
INH3
Inhibit Channel 3
7
PG4
Power Good Channel 4
8
INH4
Inhibit Channel 4
9
GINH
Global Inhibit
10
ACOK
AC ains signal
11
+5 V
Global 5 V bias
12
COM
Common