Appendix A
VXI-1501 Specifications
A-4
www.ni.com
Cooling Provided
Fan set to “Variable” .......................Quiet operation (approximately
75% airflow) at <30 °C ambient
temperature and high speed
operation at >40 °C ambient
temperature
Fan set to “High” .............................Full airflow all the time
For modules with typical density ....10 °C rise at 60 W per slot
15 °C rise at 75 W per slot
Acoustical noise
Low fan speed..................................48 dBA sound pressure at
bystander position. Lpa = 48 dB
fiktiver Arbeitsplatz, normalier
Betrieb, nach DIN 45635 T. 1
High fan speed.................................56 dBA sound pressure at
bystander position. Lpa = 56 dB
fiktiver Arbeitsplatz, normalier
Betrieb, nach DIN 45635 T. 1
Safety ......................................................Meets UL 3111-1, CAN/CSA
C22.2 #1010.1, IEC 61010-1, and
EN 61010-1
Minimum Airflow per Slot
1
2
3
4
5
6
1.0
2.0
High Fan Speed
Airflow (liters/sec)
P Across
Module
(mm H O)
2