Controller for pellet oven – NPBC-V3C-B

W

AY

 

OF

 O

PERATION

 

 

A  burner  controlled by NPBC-V3C-B  can  work  in  continuous  automatic  mode  or  in  timer  mode.
While in timer mode, the burner works only during the intervals of the day and the days of the week
set by the user. While working, it goes through several stages: cleaning, igniting, unfolding the fire,
modulated burning process according to the current and set temperature of the boiler, intermediate
cleaning performed during the burning process, extinguishing and cleaning again. The current stage of
the burner is displayed in green color on the bottom line of the main screen.

Every ignition begins with a cleaning cycle to clean all leftovers of the previous burning. At first only
the main fan works for as long as it is set in the menu 

Factory Settings → Burning Setup → Fuel X

→ Cleaning

, line 

Start

, column 

Fan

. Then the Cleaning fan also starts and works for as long as it is

set in the same menu, line  

Start

, column  

FC

. The cleaning procedure is followed by the  igniting

phase.

The  ignition procedure starts with loading the first fuel  dose in the burning chamber. The electrical
heater fires up the fuel while the fans provide the air flow. The procedure is performed in 3 stages.
During the first stage only the ignition heater works to reach the necessary temperature for ignition
faster. During the second and the third stages the ignition heater works along with the fans that provide
the necessary oxygen for the ignition and blow the heat from the heater to the fuel. It is recommended
to set lower speed for the fans during the second stage, so that they won't cool down and blow off the
flame and higher speed for the third stage to increase the air flow. To set the maximum duration of
each stage and the fans' speed go to the menu  

Factory Settings → Burning Setup → Fuel X →

Ignition

. When the photo sensor detects the light from the burning fire, the ignition heater turns off

and the burner goes to Unfolding fire phase to stabilize the fire. If the pellets do not ignite during the
set time for this, the burner loads a new portion and makes a new attempt for ignition. This happens
only for the first 3 ignition retries and the pellet portion for each of them is respectively 100%, 50%
and 25% of the set dose. After  the last attempt for ignition, the burner stops and displays an error
message for ignition fail. The parameters for the first dose and the ignition can be set in the menu as
many retries as set in the menu  

Factory Settings → Burning Setup → Fuel X → Ignition

. The

parameters  for detection  of the  burning fire  can be  set in the  menu  

Factory  Settings → Flame

Detection

The successful ignition is followed by the smooth unfolding procedures. If the burner goes instantly to
burning on 3

rd

 power level, when the fire is still unstable and the burning chamber is cold, the high air

flow from the fan might blow off or smother the flame. To avoid this, the burner waits for the first
dose of pellets to burn out and then slowly increases the power to the highest required power level
according to the temperature difference between the set temperature and the current temperature of the
boiler, starting with the lowest level P1. The parameters for the Unfolding fire process can be set from
the menu 

Factory Settings → Burning Setup → Fuel X → Unfolding Fire

The next phase is the burning control. NPBC-V3C-1 has settings for 4 different power levels. Three of
them are used for the burner's normal work. The 4

th

 power level maintains the burning fire to avoid

unnecessary cycles of extinguishing, cleaning and ignition when the water in the boiler has reached the
set temperature. Of course, if there is no need for more heat in the heating installation for longer period
of time, the burner turns off. The portion of pellets for each power level is a function of the auger
motor's capacity and activate time and the cycle between two of its turnings on. The parameters for
each power level's settings are auger motor's active time, cycle between two turnings on and main and
exhaust fans' speed. These parameters can be set in the menus 

Factory Settings → Burning Setup →

User Manual / ver 3.7

   

http://www.naturela-bg.com/en/

 

page 6 of 30

Summary of Contents for NPBC-V3C-B

Page 1: ...Controller for pellet oven NPBC V3C B Controller for pellet oven or hot air generator NPBC V3C B SOFTWARE VERSION 40 18 User Manual ver 3 7 http www naturela bg com en page 1 of 30...

Page 2: ...10 minutes or less the burner will remain off because otherwise the extinguishing procedure may begin before the fire is stabilized If OD input activates during Ignition or Unfolding procedures the e...

Page 3: ...same time A micro USB coupling on the face panel of the Control module for connection with a computer with software for direct control and monitoring The controller NPBC V3C B is designed to run burne...

Page 4: ...temperature pt100 sensor to control the temperature of the oven or hot air A potential free contact of a room thermostat for better control of the burning process according to the room temperature USB...

Page 5: ...Controller for pellet oven NPBC V3C B User Manual ver 3 7 http www naturela bg com en page 5 of 30...

Page 6: ...fire If the pellets do not ignite during the set time for this the burner loads a new portion and makes a new attempt for ignition This happens only for the first 3 ignition retries and the pellet po...

Page 7: ...hase and after that in initial state During the cleaning phase the main fan works on 100 of its power If there is an additional powerful cleaning fan or mechanical cleaning system connected to the FC...

Page 8: ...ges on the bottom line of the screen appear in different colors depending on the type of information they provide white text for the date green for the current work phase and red User Manual ver 3 7 h...

Page 9: ...d display any of the following parameters Icon Displayed information Level of illumination measured by the photo sensor Exhaust fan s speed Information about the upcoming action of the timer If there...

Page 10: ...10 Extinguishing While in Standby mode the burner doesn t work If it was working right before switching to this mode it will instantly start the extinguishing procedure It needs some time to complete...

Page 11: ...burner remains off and a warning message is displayed on the screen As soon as any of the timers is activated the burner will switch to Timers mode automatically How to change the set temperature for...

Page 12: ...xis represents the consumed pellets in kilograms Above the chart is the corresponding date for the currently displayed information and below is the total consumption for this day Information about som...

Page 13: ...e can be any of the following Idle No connection with WiFi router Access point The modem is waiting for the local WiFi network s SSID and password APAssociated The modem is connected to a router Inter...

Page 14: ...the error messages automatically disappear after the reason for the message is no longer present Others can be dismissed by holding the left navigation button for more than 2 seconds while on main sc...

Page 15: ...d the way to set the parameters in each of them Regardless the menu type if no buttons are pressed for certain time the controller goes back to the previous screen or to the main screen After adjustin...

Page 16: ...per second Press and hold the up or down navigation buttons to increase decrease a parameter s value with 5 points per second or to browse the list options in list choice menus with 5 rows per second...

Page 17: ...vailable only if the controller is equipped with a WiFi modem and connected through the Internet to the Naturela s information system Language Press the up or down navigation buttons to select the lan...

Page 18: ...mn On must be before the time in the column Off If necessary set the Off time first to provide larger range for the On setting When using timers to control the burner it is more convenient to get info...

Page 19: ...uel profile settings corresponding to the currently used fuel All parameters for each profile must be set from Burning Setup menu in Factory Settings Display Change the brightness of the display if ne...

Page 20: ...s are not enough repeat this step several times When the auger is full stop the manual feeding 3 Place a bucket or another tank at the end of the auger motor to collect the pellets 4 Start the manual...

Page 21: ...g or when changing the WiFi network Press the Menu button to exit this screen without making any changes Press the down navigation button to start the Access point mode The controller shows the follow...

Page 22: ...change the value for each position and the left and right buttons to switch between positions Confirm the code with the Menu button Some of the parameters in the Factory settings are common for all ty...

Page 23: ...city and pending time for FC output if necessary The internal auger motor always starts at the same time with the main auger and works for as long as it is set in this menu Its active time in seconds...

Page 24: ...level When the difference is between the values for P1 and P2 the burner works on 1st power level When it s less than the value for P1 the burner woks on Suspend power level While on Suspend if the d...

Page 25: ...rently editable digit is visible Use the up and down navigation buttons to set the current digit and switch to the next previous position with the right left navigation button To enable the code check...

Page 26: ...t the row Burning Setup and press the right navigation button Select the fuel type and press the right navigation button again Cleaning This menu combines the settings for all main cleaning procedures...

Page 27: ...mediately to full power because this might extinguish the unsteady fire This menu sets the process of unfolding the fire on two stages burning of the first fuel dose and smooth unfolding The upper fie...

Page 28: ...The shortest switch time interval could be the cycle between two feedings which usually is 20 30 seconds For such a short period of time the temperature of the heating installation can t change signif...

Page 29: ...ftware versions of the Control module and the Executive module The controller should display its main screen within 3 seconds If this doesn t happen and the Executive module s version is missing there...

Page 30: ...d the software in the module If the controller s version is in red there is a hardware incompatibility between the modules If the software version of the Executive module is in red there is a software...

Reviews: