Electronic pellet burner controller - NPBC-V3M

Maximum  temperature  -  

Set  Temperature

  –  adjust  the  upper  limit  of  the  range  for  the  boiler’s

temperature

Safety Setup

 – A high temperature sensor pt100 monitors the temperature of the exhaust gases. The

parameter  

Warn

 sets the value (in Celsius), above which the controller displays a warning message

Cleanup.  The parameter  

Alarm

  sets the value (in Celsius),  above which the controller displays a

message TE Alarm and turns off the burner, because the temperature of the exhaust gases is too high.
In both cases the boiler needs to be cleaned up. If the burner doesn't have a high temperature sensor
pt100, this function could be disabled by removing the check sign on the row 

Active

The following screens are available only if the burner is in Standby mode!!!

Test Fan Speed

 – test setting for fan's speed. The power of the air fan can be increased or decreased

in percents by 

 and 

▼ 

buttons.

 

This function has limited active time and turns off automatically. 

Test the Exhaust fan – 

Test EFan Speed

 – 

test setting for fan's speed. The power of the exhaust

fan can be increased or decreased in percents by 

 and 

▼ 

buttons.

 

This function has limited active

time and turns off automatically. 

User Manual / version 2.6

 

http://www.naturela-bg.com/en/

 

page 22 of 27

Summary of Contents for NPBC-V3M

Page 1: ...Electronic pellet burner controller NPBC V3M Electronic Pellet Burner Controller NPBC V3M SOFTWARE VERSION 3 3a 3 2 User Manual version 2 6 http www naturela bg com en page 1 of 27...

Page 2: ...ignition attempts 3 An option to power up the FC output during the Intermediate cleaning procedures This output may supply power to a device for periodical mechanical cleanings of the burning chamber...

Page 3: ...an for example for taking out the exhaust gases from the boiler if necessary Both blowers power can be adjusted from the controller NPBC V3M 1 has an option to control the temperature of the exhaust g...

Page 4: ...boiler Temperature sensor for the hot water heater High temperature pt100 sensor to measure the temperature of the flue gases This temperature sensor is not used to detect the burning fire but only to...

Page 5: ...Electronic pellet burner controller NPBC V3M User Manual version 2 6 http www naturela bg com en page 5 of 27...

Page 6: ...rk process keeps the set temperature In the work mode field will be shown Auto Programme This mode has additional programming periods of the day when boiler s work is allowed In this mode the burner s...

Page 7: ...35o C The difference between the temperature of the water in the boiler and in the water heater is above 5o C The temperature of the water in the water heater is lower than the temperature set in the...

Page 8: ...stat is not activated in the menu Addons Activation the temperature in the rooms is considered as not reached and the central heating circulation pump works unconditionally Summer Mode the boiler work...

Page 9: ...hich would be turning on On or turning off Off the burner Turning off the controller To turn off the controller press F and choose Standby The screen will take the following view After that an extingu...

Page 10: ...Error messages can be BB Alarm an alarm from the back burning thermistor Sensor E1 the temperature sensor in the boiler is disconnected or missing Sensor E2 the temperature sensor in the boiler is sho...

Page 11: ...indicator field and the burner goes to burning phase If the pellets do not ignite before the set time is up a new portion of pellets is loaded and a new attempt for ignition is made After as many ret...

Page 12: ...differential temperature for the first power level the burner goes to Suspend mode indicated by If the Suspend mode continues longer than the set time for this mode and there is no need of increasing...

Page 13: ...e changes made on the current screen Manual control of the feed screw motor Manual Feed By using the up or down arrow keys turn on or off the check box in front of Feed If the check box is checked the...

Page 14: ...ing Set Time Sets the clock Date setting Set Date Sets the date Contrast Sets the contrast of the LCD display Language Choose the language you prefer for the menus FACTORY SETTINGS Factory settings ar...

Page 15: ...nking parameter in the relevant direction the Enter button switches to the next editable parameter the F button saves the changes in the current menu and exits the Edit mode if no buttons are pressed...

Page 16: ...tup set the number of ignition attempts Retries the work time of the auger for initial feed Feed and the speed of the Exhaust Fan EFan Ignition cycle setup Cycle Setup adjust the work time of the heat...

Page 17: ...regulation Set the difference between the set temperature and the boiler temperature for each level 3rd level Setup adjust the work mode for 3rd power level maximum power Set the active time of the a...

Page 18: ...e time of the auger when loading a portion of pellets the cycle time before loading a new portion of pellets and the speed of the fans Settings here are the same as above Smooth extinction of the fire...

Page 19: ...duration of the procedure from the second parameter on the second line If you want to deactivate the intermediate cleaning procedures set this parameter to 0 You have the option to choose the fan that...

Page 20: ...ions If Tstat NO is checked the room thermostat will be with normally opened sockets Burner feeder active time set Burner Feeder adjust the internal auger motor s if any active time It turns on at the...

Page 21: ...culation pump DHW Pump Thermostat activates the option to work with a room thermostat External Stop Ext Stop This menu gives an option to use an external stop switch for the burner Connect this switch...

Page 22: ...both cases the boiler needs to be cleaned up If the burner doesn t have a high temperature sensor pt100 this function could be disabled by removing the check sign on the row Active The following scree...

Page 23: ...rner controller NPBC V3M Test turning on of the rest of the outputs Test Outputs When a row is checked power is supplied to this output for test purposes User Manual version 2 6 http www naturela bg c...

Page 24: ...ral Setup Retries 0 5 3 Feed seconds 1 99 10 EFan speed level 1 100 15 Ignition Cycle Setup Heater seconds 0 600 30 Fan phase 1 speed level 1 100 5 minutes 1 9 2 Fan phase 2 speed level 1 100 15 minut...

Page 25: ...g Shutdown 3rd Power Level seconds 10 300 60 2nd Power Level seconds 10 300 60 1st Power Level seconds 10 300 60 Suspend Time Suspend Time minutes 0 180 20 Overheating Max C 0 20 0 Interm Cleaning Cyc...

Page 26: ...Electronic pellet burner controller NPBC V3M NPBC_Monitor exe NPBC V3M monitoring software User Manual version 2 6 http www naturela bg com en page 26 of 27...

Page 27: ...Electronic pellet burner controller NPBC V3M SETTING ALL PARAMETERS WITH NPBC_MONITOR EXE User Manual version 2 6 http www naturela bg com en page 27 of 27...

Reviews: