RC40 Control manual
78
e0x1207
Encoder
initialization failure
The encoder position cannot
be read during initialization
Check whether the encoder
connector (Feedback) on
the panel of the control
cabinet is firmly connected
and make sure that the
controller will be restarted
after power failure
e0x1209
Bus initialization
failure
Ethercat could not scan to all
slave stations, or the robot
encoder wire harness
(Feedback) was not
connected, so the bus could
not be successfully initialized;
Check the Ethercat network
cable connection in the
controller and the feedback
cable connection on the
control cabinet panel, and
restart the controller after
power failure
e0x1771
Reach J1+ software
limit
J1 axis is currently in the
positive soft limit;
Remove robot from J1
positive limit in teach mode;
e0x1772
Reach J2+ software
limit
J2 axis is currently in the
positive soft limit;
Remove robot from J2
positive limit in teach mode;
e0x1773
Reach J3+ software
limit
J3 axis is currently in the
positive soft limit;
Remove robot from J3
positive limit in teach mode;
e0x1774
Reach J4+ software
limit
J4 axis is currently in the
positive soft limit;
Remove robot from J4
positive limit in teach mode;
e0x1775
Reach J5+ software
limit
J5 axis is currently in the
positive soft limit;
Remove robot from J5
positive limit in teach mode;
e0x1776
Reach J6+ software
limit
J6 axis is currently in the
positive soft limit;
Remove robot from J6
positive limit in teach mode;
e0x1777
Reach J7+ software
limit
J7 axis is currently in the
positive soft limit;
Remove robot from J7
positive limit in teach mode;