34 Vendor Information – Navien
Point Name
BACnet
Object Type
BACnet
Object ID
Sub31 Exhaust temperature
AI
31009
Sub31 Total time after installation
AI
31010
Sub31 Number of CH operation
AI
31011
Sub31 Total time of CH operation
AI
31012
Sub31 Current amount of gas
AI
31013
Sub31 Total amount of gas
AI
31014
Boiler On/Off command
AV
1
SH supply setpoint setting
AV
2
SH return setpoint setting
AV
3
DHW setpoint setting
AV
4
Error reset command
AV
5
Boiler setpoint in DHW operation
AV
7
Outdoor reset curve heatload setting
AV
9
Maximum outdoor temperature
setting
AV
10
Minimum outdoor temperature setting
AV
11
WWSD temperature setting
AV
12
WWSD On differential setting
AV
13
Boost interval time setting
AV
14
Cascade Initial op units setting
AV
15
CH supply min temperature setting
AV
16
CH supply max temperature setting
AV
17
CH return min temperature setting
AV
18
CH return max temperature setting
AV
19