14 CONFIGURE THE GaTEway
6.4 How to Start the Installation Over:
Clearing Profiles
1. Follow the steps outlined in
to access the gateway
web Configurator.
2. at the bottom-left of the page, click the “Clear Profiles and
Restart” button.
Once restart is complete, all past profiles discovered and/or
added via web configurator are deleted. The unit can now be
reinstalled.
6.3 BACnet: Setting Node_Offset to Assign
Specific Device Instances
1. Follow the steps outlined in
to access the gateway
web Configurator.
The Node_Offset field shows the current value (default =
50,000).
●
The values allowed for a BaCnet Device Instance can range
from 1 to 4,194,303
2. To assign a specific Device Instance (or range); change the
Node_Offset value as needed using the calculation below:
Device Instance (desired) = Node_ Node_ID
For example, if the desired Device Instance for the device is
50,001 and the following is true:
●
Device has a Node-ID of 1
Then plug the device’s information into the formula to find the
desired Node_Offset:
50,001 = Node_ 1
●
50,000 = Node_Offset
Once the Node_Offset value is input, it will be applied to all
devices as shown below:
●
Device Instance = 50,000 + Node_ID = 50,000 + 1 = 50,001
3. Click “Submit” once the desired value is entered.
Figure 20: Web Configurator Node Offset Field