35
Reference
Appendix D.1.1 Compliance with UL Regulations
For UL compliance, the following instructions must be met when
operating gateway.
●
The units shall be powered by listed LPS or Class 2 power supply
suited to the expected operating temperature range.
●
The interconnecting power connector and power cable shall:
-
Comply with local electrical code.
-
Be suited to the expected operating temperature range.
-
Meet the current and voltage rating for gateway.
●
Furthermore, the interconnecting power cable shall:
-
Be of length not exceeding 3.05 m (118.3”).
-
Be constructed of materials rated VW-1, FT-1 or better.
●
If the unit is to be installed in an operating environment with a
temperature above 65 °C, it should be installed in a Restricted
Access Area requiring a key or a special tool to gain access.
●
This device must not be connected to a LAN segment with
outdoor wiring.
Appendix D.1 Specifications
Gateway Part Number GXXX001932
Electrical
Connections
One 3-pin Phoenix connector with:
RS-485/RS-232 port (TX+/RX-/gnd)
One 3-pin Phoenix connector with:
RS-485 (Tx+/Rx-/gnd)
One 3-pin Phoenix connector with:
Power port (+/-/Frame-gnd)
One Ethernet 10/100 BaseT port
Power
Requirements
Input Voltage: 12-24 VDC or 24 VAC
Current draw: 24 VAC 125 mA
Max Power: 3 Watts
12-24 VDC 250 mA @12 VDC
Approvals
CE and FCC Class B & C Part 15,
UL 60950, WEEE compliant,
IC Canada, RoHS compliant
Physical
Dimensions
4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8 cm)
Weight
0.4 lbs (0.2 Kg)
Operating
Temperature
-20°C to 70°C (-4°F to158°F)
Humidity
10-95% RH non-condensing
Wi-Fi 802.11 b/g/n
Frequency: 2.4 GHz
Channels: 1 to 11 (inclusive)
Antenna Type: SMA
Encryption: TKIP, WPA & AES
(Specifications subject to change without notice)
Figure 40: Specifications