3

  Venting

 

 

>

 

 

  Electrical Connections

 

 

>

 

 

Vent Termination Options

Horizontal vent termination

Interior view

Intake Air

E

xhaust Gas

1

2"

 

(300mm)

 

min.

Exterior view

Vertical vent termination

Sidewall vent termination

12"min. from any 
obstruction above, 
below, left, or right

1

2"

 

(300mm)

 

min.

1

2"

 

(300mm)

 

min.

3

6

"

 

(

9

00mm)

 

min.

Concentric Vent Termination

Sidewall installation

Combustion Air

Combustion Air

1" (25mm) min

Maintain 12" min. 
clearance above 
highest anticipated 
snow level or grade.

Vent

Roof installation

Vent

Vent

Combustion Air

Maintain 12" min. 
(18" min. for Canada) 
clearance above 
highest anticipated 
snow level maximum 
of 24" above roof.

Combustion  

Air

Venting Length

3” pipe venting

2” pipe venting

8

1

3

7

2

Maximum Length 150'

Maximum number 
of elbows: 8

2-to-3-inch   

6

1

3

4

5

2

Maximum number 
of elbows: 6

Maximum Length 60'

 

e

90˚ elbow = 5 linear feet of venting

 

e

45˚ elbow= 3 linear feet of venting

 

e

90˚ elbow = 8 linear feet of venting

 

e

45˚ elbow= 4 linear feet of venting

Exhaust Vent Piping Materials

 

e

All Navien boilers are Category IV appliances.

 

e

The venting system should be approved for use with Category IV appliances (typically Type B

H

 

Special Gas Vent approved by UL 1738-S636).

 

e

Venting requirements in the USA and Canada are different (see below).

Navien recommended venting materials

Locale

Recommended Vent Materials

USA

 

e

PVC Schedule 40(Solid core)

 

e

PVC Schedule 40 or 80(Solid core)

 

e

Approved Polypropylene*

Canada**

 

e

Type B

H

 Special Gas Vent Class IIA (PVC)

 

e

Type B

H

 Special Gas Vent Class IIB (CPVC)

 

e

Type B

H

 Special Gas Class IIC (Polypropylene)

* Approved Polypropylene Systems include:

t%VSBWFOU1PMZQSP 4JOHMF8BMM7FOU114YYY7FOU114YYY
t$FOUSPUIFSN*OOP'MVF487FOU*4YYYY7FOU*4YYYY

Refer to manufacture's literature for detailed installation instructions.
** For installation in Canada, field-supplied plastic vent piping must comply with CAN

/

CGA B149.1 (latest 

edition) and be certified to the Standard For Type B

H

 Gas Venting Systems, ULC-S636. Components of this 

listed system must not be interchanged with other vent systems or unlisted pipes or fittings. All plastic 
components and specified primers and glues of the certified vent system must be from a single system 
manufacturer and must not be intermixed with another system manufacturer’s parts. The supplied vent 
connector and vent termination are certified as part of the boiler. 

External LWCO Connection  
(if required by local codes)

Power Connection

C

N

23

C

N1

0

C

N

24

C

N

25

C

o

mm

o

n

           

H

ot

Refer to your local codes to determine if an 
LWCO device is required for your system and 
ensure that the built-in device meets the 
requirements. 

120 VAC 60 Hz 
Min. 2 Amp current with proper 
grounding

 

CAUTION

Using abnormally high or low AC 
voltage may cause abnormal operation, 
thereby causing fire which reduces the 
life expectancy of this product.

 

CAUTION

Disconnect the power to 
the boiler before installing 
any wire connections on 
the main PCB. 

Safety

DO NOT touch 
the power 
cord with wet 
hands.

DO NOT allow 
the boiler to be 
exposed to 
excessive 
amounts of 
water.

Confirmation of Panel DIP Switch Settings

PCB Dip Switch 2 (Set of 8)

Front Panel Dip Switch 1 (Set of 10)

SW

Function

Setting

1

Temperature 
Control

Return 
Water

1-ON

Supply 
Water

1-OFF

7

Thermostat 
or Zone 
Controller

Unused 
(Permanent 
Space 

H

eating 

Demand)

7-ON

Used

7-OFF

8

E

xhaust 

Thermostat

Temperature 
Limit 
Unused 
(CPVC)

8-ON

Setting 
(PVC)

8-OFF

SW

Function

Setting

2

Temperature 
Unit

°C (Celsius)

2-ON

°F (Fahrenheit)

2-OFF

3

Well Pump

On

3-ON

Off

3-OFF

4 & 5

H

igh 

Altitude*

0-1,999 ft 
(0-609 m)

4-OFF,  
5-OFF

2,000-5,399 ft  
(610-1,645 m)

4-ON,  
5-OFF

5,400-7,699 ft 
(1,646-2,346 m)

4-OFF,  
5-ON

7,700-10,100 ft 
(2,347-3,078 m)

4-ON, 
5-ON

* Above 2,000 ft (610 m), the boiler will derate by 
4% for each 1,000 ft (305 m) of altitude gain.

Front Panel Dip Switch 2 (Set of 2)

SW

Function

Setting

2

Gas Type

Natural Gas

2-OFF

Propane 
Gas

2-ON