STEP 3  After Installing

  Opening All the Valves

 

>

 

Gas Valve

Space Heating System Valves

DHW System Valves

Shut-off 
valves

Shut-off valves

Power ON

Adjust Temperatures

View Basic Information

Resetting the Boiler

MOD

E

Space 

H

eating Temperature

MOD

E

D

H

W Temperature

1.  Make sure that all hot water faucets 

are closed, and ensure that the 
internal circulator and any external 
circulating pumps are off.

2.  Press the Mode button twice. The 

D

H

W mode icon turns on.

3.  Press + (Up) or – (Down) buttons 

until the desired temperature 
appears on the display.

Note

D

H

W temperature higher 

than 125°F can cause 
scalding.

MOD

E

MOD

E

When the power is on, the water 
temperature of the space heating 
supply will appear with the water 
pressure on the front panel display 
in 5 second intervals.

1.  Press the Mode button once. The 

space heating icon turns on. 

2.  Press the + (Up) or – (Down) 

buttons until the desired 
temperature appears on the 
display.

1.  Press the Mode button three 

times. “INFO” will appear on the 
display.

2.  Press the + or – buttons to 

switch between the information 
types.

If an error message appears, you can 
try resetting the boiler to resolve the 
problem.

Note

If resetting does not 
solve the problem, refer 
to the troubleshooting 
section of the User’s 
Information Manual or 
contact the service 
center.

1

Open

Closed

2

Open a hot water 
faucet. The boiler 
should turn on and 
the gas in the gas 
supply line will be 
purged.

1

1

2

3

3

4

Shut off the manual gas valve.

Leave the faucet on until the boiler shuts down 
due to a lack of gas supply, and then turn off the 
hot water faucet.

Remove the front cover by 
loosening the 4 screws.

Loosen the screw indicated in the figure and 
connect a manometer to the pressure port. 
Reset the manometer to zero before use.

5

Открыть

Re-open the manual 
gas valve and check 
for leaks.

Open multiple 
fixtures that have 
high flow rates, such 
as bathtub and 
shower faucets, to 
ramp the boiler up to 
its maximum firing 
rate.

6

NG: 3.5”–10.5” WC

LP: 8.0”–13.5” WC

Recommended Gas Pressure Settings:

          Check the inlet gas pressure reading on the manometer.

If not,

Gas supply

Adjust the inlet gas pressure with gas 
regulator.

 

CAUTION

The boiler cannot function properly without sufficient inlet gas pressure. 

Measuring the inlet gas pressure should be performed by a licensed 

professional only.

Navien, Inc. 
20 Goodyear, Irvine, CA 92618 
Tel: 1-800-519-8794, Fax: 1-949-420-0430 
www.navien.com

  Installing the Front Cover

 

>

 

1

2

2

  Ensure Maximum Water Flow

 

>

 

After running the boiler for the first 10 minutes, turn it off and clean the cold water filter 
and the space heating return strainer to remove any trapped debris.

  Final Check

 

>

 

A trial run should be performed in accordance with the Installation checklist listed in 
the boiler’s Installation & Operation Manual.

  Operating the Boiler

 

 

>

 

 