102 NCB Service Manual
Version 1.0
5.2.12 218Error
Error conditions and Check Items
Error
Description
E218
Heat exchanger
input
temperature
sensor open
If an error (open: 14°F (-10°C) or lower) in the heat exchanger input temperature sensor is detected, the system
displays the 421E error on the front panel. If this occurs, the boiler initiates shutdown.
Check items
1.
Check if the heat exchanger input temperature sensor connector is wet due to any reason, including
leakage.
2.
Replace the defected heat exchanger input temperature sensor.
3.
Replace the controller.
Is the inlet thermistor
normal?
Resistance between #3 and #4 of CN13 is from
0.437k
Ω
to 176k
Ω
at normal condition.
(see page 56 for Wiring Diagram)
Check connector
(#3 and #4 of CN 13)
Replace inlet thermistor
Before measuring resistance of the thermistor,
detach the connector from the PCB.
NO