General Specifications
NOTE
This unit may be installed at elevations up to 10,100 ft (3,078 m) for use with Natural Gas, and up to 4,500 ft (1,370 m) for use
with Propane.
Item
NCB-180
NCB-210
NCB-240
Dimensions
17 in (W) x 28 in (H) x 12 in (D)
Weight
74 lbs (34 kg)
84 lbs (38 kg)
84 lbs (38 kg)
Installation Type
Indoor Wall-Hung
Venting Type
Forced Draft Direct Vent
Ignition
Electronic Ignition
Natural Gas Supply Pressure (from source)
3.5 in-10.5 in WC
Propane Gas Supply Pressure (from source) 8.0 in-13.5 in WC
Natural Gas Manifold Pressure (min/max)
-0.07 in WC / -0.66 in WC
-0.05 in WC / -0.36 in WC
-0.06 in WC / -1.2 in WC
Propane Gas Manifold Pressure (min/max)
-0.06 in WC / -0.62 in WC
-0.1 in WC / -0.66 in WC
-0.03 in WC / -0.98 in WC
Gas Connection Size
3/4 in NPT
Power Supply
Main Supply
120V AC, 60Hz
Maximum Power
Consumption
200W (max 2A)
Materials
Casing
Cold-rolled carbon steel
Heat Exchangers
Primary Heat Exchanger: Stainless Steel
Secondary Heat Exchanger: Stainless Steel
Domestic Water Heat Exchanger: Stainless Steel
Venting
Exhaust
2 in or 3 in PVC, CPVC, Polypropylene
2 in or 3 in Special Gas Vent Type BH (Class III, A/B/C)
Intake
2 in or 3 in PVC, CPVC, Polypropylene
2 in or 3 in Special Gas Vent Type BH (Class III, A/B/C)
Vent Clearances
0 in to combustibles
Safety Devices
Flame Rod, APS, Gas Valve Operation Detector, Ignition Operation Detector, Water
Temperature High Limit Switch,
Exhaust Temperature High Limit Sensor
Accessories
Plumb Easy Valve Set, Outdoor Sensor, Pressure Relief Valve, Condensate Neutralizer,
Communication Cable
Summary of Contents for NCB-180
Page 3: ......
Page 16: ......
Page 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Page 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Page 142: ...Memo...
Page 143: ...140 NCB Service Manual Version 1 0 Memo...
Page 144: ...Memo...
Page 145: ...142 NCB Service Manual Version 1 0 Memo...
Page 146: ...Memo...
Page 147: ...144 NCB Service Manual Version 1 0 Memo...
Page 148: ...Memo...