in Cubic Feet (ft
3
) per Hour (0.60 Specific Gravity; 3.0” WC Pressure Drop). Contact your gas supplier for BTU/ft
3
ratings. Use 1,000
BTU/ft3 for simplified calculations. This table is recommended for supply pressures of 6” WC or greater.
Pipe
Size
Length (including fittings)
10'
(3m)
20'
(6m)
30'
(9m)
40'
(12m)
50'
(15m)
60'
(18m)
70'
(21m)
80'
(24m)
90'
(27m)
100'
(30m)
125'
(38m)
1/2"
454
312
250
214
190
172
158
147
138
131
116
3/4"
949
652
524
448
397
360
331
308
289
273
242
1"
1,787
1,228
986
844
748
678
624
580
544
514
456
1
1/4"
3,669
2,522
2,025
1,733
1,536
1,392
1,280
1,191
1,118
1,056
936
1
1/2"
5,497
3,778
3,034
2,597
2,302
2,085
1,919
1,785
1,675
1,582
1,402
2"
10,588 7,277
5,844
5,001
4,433
4,016
3,695
3,437
3,225
3,046
2,700
2
1/2"
16,875 11,598 9,314
7,971
7,065
6,401
5,889
5,479
5,140
4,856
4,303
3"
29,832 20,503 16,465 14,092 12,489 11,316 10,411 9,685
9,087
8,584
7,608
4"
43,678 30,020 24,107 20,632 18,286 16,569 15,243 14,181 13,305 12,568 11,139
Maximum Liquefied Propane Delivery Capacity
in Thousands of BTU/H (0.5” WC Pressure Drop)
Pipe
Size
Length (including fittings)
10'
(3m)
20'
(6m)
30'
(9m)
40'
(12m)
50'
(15m)
60'
(18m)
80'
(24m)
100'
(30m)
125'
(38m)
150'
(45m)
175'
(53m)
200'
(60m)
250'
(76m)
1/2"
291
200
160
137
122
110
101
94
89
84
74
67
62
3/4"
608
418
336
287
255
231
212
197
185
175
155
140
129
1"
1,150
787
632
541
480
434
400
372
349
330
292
265
243
1 1/4"
2,350
1,620
1,300
1,110
985
892
821
763
716
677
600
543
500
1 1/2"
3,520
2,420
1,940
1,660
1,480
1,340
1,230
1,140
1,070
1,010
899
814
749
2"
6,790
4,660
3,750
3,210
2,840
2,570
2,370
2,200
2,070
1,950
1,730
1,570
1,440
NOTE
For installations using CSST (flexible) gas piping, please refer to the sizing charts provided by the manufacturer.
The use of single-stage regulators are recommended. Dual-stage regulators could cause operational issues with the boiler.
Summary of Contents for NCB-180
Page 3: ......
Page 16: ......
Page 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Page 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Page 142: ...Memo...
Page 143: ...140 NCB Service Manual Version 1 0 Memo...
Page 144: ...Memo...
Page 145: ...142 NCB Service Manual Version 1 0 Memo...
Page 146: ...Memo...
Page 147: ...144 NCB Service Manual Version 1 0 Memo...
Page 148: ...Memo...