CAUTION
If you enter an incorrect password 10 times or make no input 5 minutes, the boiler will return to the Normal Mode.
To return to the previous mode, press the Reset button.
The Factory default password is “1234”
If you make no adjustment for 10 seconds in the Parameter Edit mode, the current parameter value will be saved
automatically.
Press and hold the Reset button in Parameter Edit mode for 5 seconds to reset all settings to their default values.
When you reset one of the following parameters, the corresponding parameter will be reset automatically.
Supply absolute MIN or MAX
Return absolute MIN or MAX
Lowest Outdoor Temperature or Highest Outdoor Temperature
Item
Description
Display
(A) Outdoor Reset
Use Setting
This mode is used to configure the Outdoor Reset Control mode.
This mode is disabled by default from the factory.
Outdoor Reset in use
Outdoor Reset not in
use
(B) Outdoor Reset
Heat Road
Setting
This mode is used to configure the heat load type to be used with the
Outdoor Reset Control mode.
A preset or user-defined temperature range is selected automatically based
on the heat load type selected.
Heat Load
Supply Set-
point Range
Return Set-
point Range
Remarks
1. Finned Tube
Baseboard
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
Default
2. FAN Coil
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
3. Cast Iron
Baseboard
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
4. Low Mass
Radiant
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
5. High Mass
Radiant
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
6. Radiator
120-180
℉
(48.5-82
℃
)
120-180
℉
(48.5-82
℃
)
7. Custom
Supply
Control
Absolute
MIN/MAX Set-
Point
Return Control
Absolute
MIN/MAX Set-
Point
User-
Defined
Heat loads 1-6 show the preset temperature ranges based on the load type
selected, while heat load 7 provides a custom temperature range. When the
custom temperature range is in use, the boiler operates based on the user-
defined “Absolute Min” and “Absolute Max” temperature settings.
Outdoor Reset heat
road types (1-7)
Outdoor Reset heat
load not selected
Summary of Contents for NCB-180
Page 3: ......
Page 16: ......
Page 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...