4.9.2 High Limit Switch
Check Point
Check Point
Function
1.
Overheat prevention switch.
2.
If the unit detects extremely high temperatures, it will automatically trip and shut down the unit.
3.
Excessively high water temperatures (more than 197.6 °F or 92 °C) in heat exchanger will activate
the high limit switch.
Failure Event
Unable to detect excessively high water temperature if switch fails.
Effects
Unable to shut down the boiler if the water temperature from the heat exchanger exceeds 197.6
°
F
(92
°
C).
Error Code
E016, E046
Diagnostic
1.
Visual inspection: Connection and/or breakage of wires.
2.
Resistance check: Check range of resistance shown below.
Color/Number of wires
Resistance range : under 1.0
Ω