30 Installing the System Piping
3.6.4 System Application - Air Handler System
Air Separator
Expansion Tank
Air Flow
Air Handler
Note
●
The boiler performs automatically System
application drawings are intended to
explain the system piping concept only.
●
Refer to 3.4 System Fill Connection on
page 25 for make-up fill connections
and refer to the requirements of your local
codes to ensure compliance.
●
Boiler side piping to the air handler
which exceeds the capabilities of the
internal boiler circulator requires primary/
secondary piping configuration with a
separate system circulator.
●
Air handlers with an internal circulator
shall be piped either with a crossover pipe
at the AHU or in a primary/secondary
configuration with the boiler.
Wiring Diagram
CN23
CN10
CN24
CN25
Common Hot
Thermostat
<Air Handler>
<NCB>