Venting the Boiler 41
Indoor Boiler Installation Venting Examples
The following are some possible indoor venting options:
●
2 in or 3 in Two-pipe Sidewall Venting
12" (300mm) min.
12" (3
00mm
) min.
Exhaust Gas
Exhaust Gas
Intake Air
Exterior View
Intake Air
Intake Air
5.4 Terminating the Vent
Before installing the boiler, determine what type of vent
termination is appropriate for the installation location and
situation. The subsections that follow describe some typical
venting configurations.
CAUTION
Minimum Clearance to Metering devices and Relief
equipment.
Maintain a minimum horizontal clearance of 4 ft
(1.22 m) from electric meters, gas meters, regulators, and relief
equipment. Do not install the boiler above or below electric
meters, gas meters, regulators, or relief equipment unless a 4 ft
(1.22 m) horizontal clearance is maintained.