24 Troubleshooting
If resetting the boiler and attempting the remedies suggested below do not resolve the problem, contact an
authorized technician, a licensed professional, or Technical Support at 1-800-519-8794 for service instructions.
Problem
Possible Cause(s)
What to do
No water comes
out when the
hot water tap is
opened.
●
Is the domestic cold inlet filter
clean?
●
Is an error code displayed on the
front panel?
●
Is the boiler frozen?
●
Ensure that the shut–off valves on the hot
and cold pipes are open.
●
If an error code is displayed, refer to
“5.2 Understanding Error Codes” on
The water from the
hot water faucet is
cold or turns cold
and stays cold.
●
Is the hot water faucet open wide
enough draw at least 0.5 gallons of
water per minute (GPM) through
the boiler?
●
Is an error code displayed on the
front panel?
If an error code is displayed, refer to
“5.2 Understanding Error Codes” on page 25.
The water from the
hot water faucet is
not hot enough.
Is the set temperature too low?
●
Check the boiler’s temperature setting. Refer
to See “3.2 Adjusting the Temperature” on
●
Check for cross piping between the heating
supply and heating return lines.
The water from the
hot water faucet is
too hot.
Is the set temperature set too high?
Check the boiler’s temperature setting. See “3.2
Adjusting the Temperature” on page 10.
Space heating side
malfunction
Is the setting temperature too low?
Check the boiler’s temperature setting. See “3.2
Adjusting the Temperature” on page 10.
Is there power to the system, or is the
system in stand by?
Make sure the power is on, and plugged into
the outlet with the correct voltage. Press the
Power button ( ) and raise the setting
temperature. Make sure the boiler is turned on.
Is the system running for domestic hot
water (DHW)?
When the unit is heating for DHW, the heating
side does not work.
Is the filter on the heating side
restricted?
Clean out filters that belong to the heating
side.
5. Troubleshooting
5.1 Solving Basic Problems
If you experience a problem with the boiler, refer
to the following chart for possible remedies. Error
codes that appear on the front panel display are
explained in the following section.
For minor problems, resetting the boiler may resolve
the issue. To reset the boiler, press the Back button
(
) on the front panel.