18 Technical Data
Specifications
Unit
NCB700-2S+/42K
NCB700-3S/54K
Appliance protection rating
-
IPX4D
Boiler mounting system type
-
Wall-mounted
Flue exhaust/Air intake system types
-
B23, C13, C33, C53
Flue exhaust/Air intake system diameters
mm
Coaxial Ø60/100 and Ø80/125
Max. gas pipe pressure drop
Pa
294
294
Max. horizontal coaxial length Ø60/100
m
20
Max. vertical coaxial length Ø60/100
m
21
Equivalent elbow length @ 90° Ø60/100
m
2.4
Equivalent elbow length @ 45° Ø60/100
m
1.2
Max. horizontal coaxial length Ø80/125
m
68
Max. vertical coaxial length Ø80/125
m
70
Equivalent elbow length @ 90° Ø80/125
m
2.4
Equivalent elbow length @ 45° Ø80/125
m
1.2
Equivalent length of adapter Ø60/100 => Ø80/125
m
0.5
Hydraulic connection diameter
mm
22
mm
15
mm
22
Dimensions (Width x Depth x Height)
mm
440x335x695
Total boiler weight (lift weight)
kg
39
42
Summary of Contents for NCB-700-2S+/42K
Page 3: ......
Page 4: ...Revisions 3 Version Description of changes Date 1 00 First issue July 11 2022 Revisions...
Page 119: ...Memo...
Page 120: ...Memo...
Page 121: ...Memo...