System Details 59
4.7.17 Dual venturi
Item
Description
Function
Controls the TDR by adjusting the gas / air mixture rate.
A synchronous motor is used to provide two control phases for mixing gases.
Fault
1. Blades will not close.
2. Blades will not open.
Symptoms
1. Boiler operation starts and stops frequently because of excessive heat supply.
2. Set point temperature is not reached because of insufficient heat.
Error codes
E060
Diagnostics
Voltage test: Test the voltage at the synchronous motor.
(After approx. 2 sec the blade opening or closing, the motor turns off.)
<Closed>
<Open>