System Details 37
4.4.8.5 Setting the Special Operation Modes
To operate the boiler in special operation modes, press the Back
button (
) and the Menu button (
) simultaneously for
3 seconds, and then select “5. Special Operations”.
Press the Up button (
) or the Down button (
) to switch
between the operation modes. Press the OK button (
) to
select an operation mode.
The boiler resumes operation in normal operation mode if no
input is detected for 3 hours.
Press the Back button (
) to return to the previous screen or
menu.
Item
Description
1. Normal
Set the boiler to run in normal
operation mode.
2. MIN
Set the boiler to run in
minimum operation mode.
3. CH MAX
Set the boiler to run in central
heating maximum operation
mode.
4. DHW MAX
Set the boiler to run in DHW
maximum operation mode.
Item
Description
3. 3 Way Valve
Test the 3 way valve operation.
●
The 3 way valve is turned on
as soon as you enter the test
mode.
●
Press the OK button (
) to
toggle the valve operation
[On (DHW) -> Off (CH)/Off
(CH) -> On (DHW)].
4. Dual Venturi
Test the dual venturi operation.
Press the OK button (
)
to toggle the dual venturi
operation [On (DHW) -> Off (CH)
-> On (DHW)].
5. Flow control Valve
Test the flow control valve
operation. Rotate the valve
from its current position to fully
(0%), then fully closed (100%)
and then back to the stating
position.
6. Mixing Valve
Test the mixing valve operation.
Rotate the valve from its current
position to fully (0%), then fully
closed (100%) and then back to
the stating position.
7. Recirc Pump (DHW)
Test the recirculation pump
(DHW) operation. Press the
OK button (
) to toggle the
pump operation [On -> Off ->
On].