58 Troubleshooting
Error Code Sub Code
Function
Diagnosis/Actions
E205
1
Heating supply thermistor open
error
1. Check the thermistor.
2. Check pump wiring connections.
2
Heating supply thermistor short
error
E218
1
Heating return thermistor open
error
1. Check the thermistor.
2
Heating return thermistor short
error
E291
3
Supply / Return inversion limit
Check the direct water connection.
E302
0
Low water pressure
1. Check filling link and pressurise system to 1.0 - 1.3 bar.
2. Check the incoming water pressure and activity at the PRV.
E352
0
High water pressure
1. Check filling link is not open and filling the system.
2. Check the incoming water pressure and activity at the PRV.
E353
1
Water pressure sensor open error
Check the water pressure sensor.
2
Water pressure sensor short error
E407
1
Hot water outlet thermistor open
error
1. Check the thermistor.
2. Replace the thermistor.
2
Hot water outlet thermistor short
error
E421
1
Cold water inlet thermistor open
error
1. Check the thermistor.
2. Replace the thermistor.
2
Cold water inlet thermistor short
error
E434
1
Abnormal operation: Flow control
value
E441
1
DHW Outlet 2 thermistor open or
short circuit
E445
1
Abnormal operation: Mixing valve
E480
1
DHW tank thermistor open circuit
2
DHW tank thermistor short circuit
E515
Abnormal operation: Relay
feedback (PCB)
E517
0
Abnormal operation: DIP switch
setting (PCB)
Check the dip switches on the front panel and the PCB.
E594
0
Abnormal operation: EEPROM
(PCB)
Check the PCB.
E615
Abnormal operation: Input and
memory (MCU)
E740
1
Abnormal operation: Outdoor
temperature sensor
1. Ensure that outdoor reset curve is correctly configured.
2. Check the outdoor temperature sensor’s wiring connections.
E782
0
Abnormal operation: Main panel
communication
Check the PCB.