background image

26        Connecting the Gas Supply

WARNING

 

If a gas type other than the one specified on the boiler 

reference plate is used, it could cause a fire or even an 

explosion.

 

It is important to ensure that the gas supply is suitable 

for the type and capacity of the boiler.

 

Thoroughly check the seal and draining of the entire 

installation, as a gas leak could cause serious damage.

DANGER

 

Gas leaks can cause explosions resulting in serious 

personal and material damage.

 

Keep all doors and windows open while you are bleeding 

the gas pipes and put out any cigarettes, flames or other 

possible source of ignition.

For the installation of any type of gas, the installer must be 

authorised by the Ministry of Industry and strictly follow the 

applicable Gas Regulations. The gas installation must comply 

with the Gas Installation Regulation.

However, the following recommendations must be complied 

with, at the least:

 

Before installing the gas pipes, check the type of gas is 

compatible with the boiler.

 

Check that the gas meter in the home can measure the rate of 

gas supply required.

 

The gas pipe diameter is not determined by the boiler 

connection. It should be calculated in accordance with its 

length and consequently its pressure drop.

 

The pipes must be directly connected to the main gas supply 

pipe, not connected in parallel to other gas appliances.

 

Check there are no leaks from the installation.

 

The gas supply company is solely responsible for connecting 

the gas meter to the gas installation.

To connect the gas supply:

1.  Connect the gas supply pope to the connection located on 

the underside of the appliance.

2.  After completing the gas installation, check there are no 

leaks and bleed the air from all the pipes, following the 

procedures described in the applicable standards to this 

respect.

Gas Shutoff Valve

Gas Supply

Union

Bottom View

Gas Inlet Adapter

Union

5.    Connecting the Gas Supply

Summary of Contents for NCB700-42C

Page 1: ...warranty service always contact an official Technical Assistance Service TAS first Contact the technician or professional who installed your boiler Contact a Gas Safe Registered engineer When contact...

Page 2: ...actly a fire or explosion may result causing property damage or personal injury Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance WHATTO...

Page 3: ...Terminating the Flue 34 7 Setting the DIP Switches 35 7 1 PCB DIP Switches 35 7 2 Front Panel DIP Switches 35 8 Connecting Electrical Supplies 36 8 1 Accessing the Terminal Strips 36 8 2 Connecting t...

Page 4: ...bour s phone call your gas provider and follow their instructions If you cannot reach your gas provider call the fire department Do not return to your home until authorised by your gas supplier or the...

Page 5: ...explosion Do not place combustibles such as newspapers or laundry near the boiler or flue system Doing so may result in a fire Do not place or use hair sprays spray paints or any other compressed gas...

Page 6: ...C Very low scald risk CAUTION Do not turn on the boiler unless the water and gas supplies are fully opened Doing so may damage the boiler Do not turn on the water if the cold water supply shut off va...

Page 7: ...as If LPG conversion is required use the conversion kit supplied with the boiler and attach the item matching the LPG GC No included in the kit The Codes of good practice and regulations refer to the...

Page 8: ...s When you no longer wish to use the boiler disable any parts that could be potentially hazardous A B C D E F G 2015 811 2013 dB kW A A A B C D E F G A A KD Navien NCB 24LDWE XL 20 40 Installation Ope...

Page 9: ...ey with burner switched on 1 9 1 9 Seasonal efficiency rate SEDBUK 2009 89 1 89 1 NOx Classification Class 6 Category II2H3P Type Heating and instantaneous hot water production Heat output adjustment...

Page 10: ...ow length 90 60 100 m 1 3 Equivalent elbow length 45 60 100 m 1 0 Max horizontal coaxial length 80 125 m 68 Max vertical coaxial length 80 125 m 70 Equivalent elbow length 90 80 125 m 2 2 Equivalent e...

Page 11: ...load elmin kW In standby mode PSB kW Other items Standby heat loss Pstby kW Ignition burner power consumption Pign kW Annual energy consumption QHE GJ Sound power level indoors LWA dB Emissions of nit...

Page 12: ...ollowing diagram shows the key components of the boiler Component assembly diagrams and particular parts lists are included in the Appendices Fan Motor Front Panel Flue Duct Ignitor Flame Rod Circulat...

Page 13: ...Single Venturi Mixing Chamber Air Pipe Primary Heat Exchanger Secondary Heat Exchanger Return Adapter Filter Assembly 3 Way Valve Central Heating Return Pressure Relief Valve Central Heating Supply D...

Page 14: ...About the Boiler 13 NCB700 54C Fan Motor Front Panel Flue Duct Ignitor Flame Rod Circulation Pump Condensate Trap PCB...

Page 15: ...Single Venturi Mixing Chamber Air Pipe Primary Heat Exchanger Secondary Heat Exchanger Return Adapter Filter Assembly Gas Valve Central Heating Return Pressure Relief Valve Central Heating Supply DHW...

Page 16: ...95 mm 440mm Supply Connections Description Diameter A Flue exhaust Air intake 60 100 80 125 B Central heating supply 22 mm C Hot water outlet DHW 15 mm D Gas supply inlet 22 mm E Cold water inlet DHW...

Page 17: ...enu and select 2 Central Htg Operation by pressing the OK button 2 In the Central Htg Operation menu select 1 Central Htg ON OFF and select Enable Then select 1 1 CH Set Temp and select a heating temp...

Page 18: ...ture range by k factor setting value and the applicable outdoor temperature range 20 15 10 5 0 10 15 20 25 5 20 30 40 50 60 50 70 80 90 4 3 5 3 2 5 2 1 5 1 2 0 6 1 0 2 Outdoor Temperature C Outdoor Te...

Page 19: ...boiler in its final location A detailed description is given of the procedure in the sequenced sections below Wall mounting Gas connection Electrical connections DIP switch settings Final check Water...

Page 20: ...ainage The boiler produces a significant amount of condensate during operation This condensate must be removed from the boiler and suitably treated if national legislation so requires The boiler shoul...

Page 21: ...boiler in areas where petrol or other flammables are used or stored Ensure that combustible materials are stored away from the boiler and that hanging laundry or similar items do not obstruct access...

Page 22: ...the tongues on the mounting bracket and hang the boiler on the bracket When mounted with the mounting bracket the boiler will have a 16 mm clearance from the back of the wall WARNING The boiler is he...

Page 23: ...d cause leaks Any dirt in the tubes could reduce boiler efficiency and cause it to malfunction Any pipes exposed to the elements or which could freeze in winter must be insulated with suitable insulat...

Page 24: ...3 5 Follow all local codes and regulations when disposing of condensate from the boiler We recommend draining the condensate into a laundry tub as the alkali in laundry detergent will neutralise the...

Page 25: ...terial for the drain line such as PVC or CPVC Do not reduce the size of the drain line to less than 21 5 mm The drain line can be connected to the condensate trap using a condensate trap hose The hose...

Page 26: ...e normally after performing an air purge 4 7 Testing the Water System WARNING Ensure that the boiler is full of water before firing the burner Operating the unit without filling it will damage the boi...

Page 27: ...owing recommendations must be complied with at the least Before installing the gas pipes check the type of gas is compatible with the boiler Check that the gas meter in the home can measure the rate o...

Page 28: ...lace away from direct sunlight It must also be thoroughly secured to prevent it from tipping over which could cause an explosion If the boiler is used with propane a gas regulator suitable for this ty...

Page 29: ...t gas pressure reading on the manometer The gas pressure must fall within the ranges specified on page 8 3 Leave the faucet on until the boiler shuts down due to a lack of gas supply and then turn off...

Page 30: ...connecting the flue outlet must be correctly joined using sealing gaskets Ensure that there are no leaks from any part of the removal circuit Switch off the boiler and wait for the pipes to cool down...

Page 31: ...ear any overhangs 6 2 Selecting a Flue System WARNING The gas removal ducts must not be in contact with or near flammable materials and they must not pass through any structures or walls of buildings...

Page 32: ...00 or 1 000 851 140 min Wall Extended Removal System 80 125 Max length A B 1 x 90 elbow 68 2 2 65 8 m 60 100 Max length A B 1 x 90 elbow 20 1 3 18 7 m B A 80 125 Max length A B 1 x 45 elbow 68 1 67 m...

Page 33: ...System 80 125 Max length A B 1 x 45 elbow 70 1 69 m 60 100 Max length A B 1 x 45 elbow 21 1 20 m A B Minimum 350 mm Pipe Diameter mm Maximum Length m Elbow Equivalent Length m 60 100 21 45 1 0 80 125...

Page 34: ...110 2 x 1 4 107 2 m D C A B Minimum 370 mm Pipe Diameter mm Maximum Length m Elbow Equivalent Length m 80 80 110 45 1 4 Extended Removal System 80 80 Max length A B C D E F 4 x 90 elbow 110 4 x 2 2 10...

Page 35: ...l terminal The total length of the tubes must not exceed the maximum value defined If the removal installation includes elbows while calculating the total length you must take into account that each e...

Page 36: ...board configures boiler type capacity burner type country and discharge of condensate function 1 2 3 4 5 6 7 8 ON DIP SW1 Switch Function Setting 1 Boiler Type SOLO ON COMBI OFF 2 Reserve 3 4 Capacity...

Page 37: ...t the time of installation Note The NCB700 boiler has an electrical protection degree of IPX5D The electrical connection must be made via a bipolar switch located on the same premises as the boiler Th...

Page 38: ...ether with the seal B 4 Insert all these elements in the cable gland and press on the lid A until the cable is sufficiently fixed in place and the unit is sealed Note The boiler must be connected to t...

Page 39: ...lock is not required Simply connect the Navien Smart Room Controller cable to the 2 pin connector Note You need to install an app on your mobile device to control the boiler from your mobile device Re...

Page 40: ...ngeover check the gas inlet pressure Check that the gas circuit is hermetically sealed Check that the control panel is working correctly Check that it functions normally when the boiler is switched on...

Page 41: ...r s schedule programming operation is set f DHW preheat Displayed when the DHW preheat feature is enabled DHW preheat DHW Intelligent DHW preheat Always on DHW preheat Weekly DHW preheat off Eco mode...

Page 42: ...al heating and DHW supply temperatures Refer to the following table for detailed information a b c d e f a Menu button Access to the Main menu screen b Back button Access to the previous screen c OK b...

Page 43: ...rt up wizard The temperature will appear on the front panel display after the power is turned on 10 3 Start Up Wizard The setup wizard should run the first time the unit is powered on The wizard must...

Page 44: ...r temperature 1 Make sure that all hot water taps are closed and ensure that the internal circulator and any external circulating pumps are off 2 In normal operation mode press the Up button The DHW t...

Page 45: ...ote The fan motor controls the APS so the fan target speed Fan Target RPM is only for your reference 10 6 Accessing Basic Menu Items In the Main Menu screen you can view the boiler s operating conditi...

Page 46: ...input from the outdoor temperature sensor OTC Outdoor Temperature Compensation control will be enabled automatically Also if there is no input from the outdoor temperature sensor OTC control will be d...

Page 47: ...gramming operation press the Menu button and then select 4 Schedule Programming 10 6 3 Setting the DHW Operation To set the boiler s DHW operation press the Menu button and then select 3 DHW Operation...

Page 48: ...ch between the list items or to increase decrease setting values Press the OK button to select an item or to confirm after making changes Press the Back button to return to the previous screen or menu...

Page 49: ...System Information To view the miscellaneous system information press the Menu button and then select 6 EMS Data Press the Up button or the Down button to switch between the information items Press t...

Page 50: ...u Items 10 7 1 Viewing Service Information To view the service information about the boiler press the Back button and the Menu button simultaneously for 3 seconds and then select 1 Service Status Info...

Page 51: ...20 min Default 3 min 8 Freeze protection Set the pump freeze protection temperature Setting range 6 C 10 C Default 10 C Note The system freeze protection temperature is set based on the pump freeze p...

Page 52: ...it Setting range Central heating minimum capacity central heating minimum capacity limit 20 Default Boiler s minimum heat capacity 11 CH Max Limit Set the central heating maximum heat capacity limit S...

Page 53: ...iler to run in 2nd stage minimum operation mode Press the Up button or the Down button to switch between the test procedures Press the OK button to run a test procedure Note During the test mode the b...

Page 54: ...E353 Abnormal operation Water pressure sensor Auto DHW Circulation E407 DHW Outlet thermistor Open or Short Circuit Alarm E421 DHW Inlet thermistor Open or Short Circuit Auto E434 Abnormal operation F...

Page 55: ...l need to drain either both the central heating side and domestic hot water DHW side or one side only before performing maintenance tasks such as cleaning the adapter filter or to prevent the boiler f...

Page 56: ...s still connected Do not close the gas valve except for routine maintenance as this will limit additional freeze protection If the boiler will not be used for an extended period drain the boiler If th...

Page 57: ...beginning of every heating season and or when there is a problem 11 5 Maintenance Schedules Owner maintenance Daily Check boiler area Check pressure temperature gauge Monthly Check flue piping Check...

Page 58: ...may also cause severe property damage 1 Inspect all water and gas piping and verify to be leak free 2 Look for signs of leaking lines and correct any problems found Checking the Flue System and Air P...

Page 59: ...Remind the owner to follow the proper shutdown procedure and to schedule an annual start up at the beginning of the next heating season WARNING Failure to inspect for the above conditions and have th...

Page 60: ...ive is engaged in and is responsible for the connection utilization repair or servicing of gas utilization equipment or accessories who is experienced in such work familiar with all precautions requir...

Page 61: ...ssembly 8 With the internal components exposed locate the gas inlet pipe and the gas valve in the middle of the unit as shown in Figure 2 1 and Figure 2 2 Gas Valve Gas Inlet Pipe Figure 2 1 NCB700 42...

Page 62: ...exposed remove the two screws that hold the part in place Remove the Gas Orifice from its housing and prepare the new Gas Orifice for the LP conversion for installation Remove 2 screws here Figure 4 A...

Page 63: ...inal position and use all screws to secure all connections Note Do not overtighten as this may damage or crack the components 12 Check the labels carefully and then connect all the wires 13 Set the fr...

Page 64: ...value is not within 0 5 of the value listed in Table 2 the gas valve set screw will need to be adjusted If adjustment is necessary locate the set screw as shown in Figure 8 Using a 5 32 in or 4 mm All...

Page 65: ...off To properly maintain the boiler you should clean the heat exchanger annually To clean the heat exchanger 1 Press the Power button on the front panel to turn off the boiler 2 Disconnect the power s...

Page 66: ...the front panel Note When removing the front panel label all wires and make sure all wires are disconnected 7 Use a Phillips screwdriver to remove the four screws where gas inlet pipe is attached to t...

Page 67: ...important to keep electric parts of the boiler safe from water Navien recommends to use a hose If the water pressure of the hose is too high water may splash to other electric parts of the boiler Kee...

Page 68: ...emp Dip s w 8pin Dip s w 4pin EXT Contact M 7 6 5 4 3 2 1 8 MIX V V CN 10 OUTLET _Temp 5 4 3 6 2 CN 12 M HTL APS INLET_Temp 2 3 4 CN 8 1 CN 2 M 7 6 5 4 3 2 1 8 WAV V V CN 11 P E 1 2 3 4 1 6 7 8 5 1 0...

Page 69: ...68 Appendices 12 4 Ladder Diagram 3 15A...

Page 70: ...ensor is on a North or Northeast side of a structure under eaves where the sensor is shielded from direct sunlight Avoid placing sensor in close proximity of heat sources that may affect correct tempe...

Page 71: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 72: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Page 73: ...Memo...

Page 74: ...Memo...

Page 75: ...Memo...

Reviews: