24 |
Technical Specifications |
Loop S User Manual
Technical Specifications
Egon+ board
!
Warning:
IGNITION PROTECTED
ONLY WHEN EQUIPPED WITH
IGNITION PROTECTED FUSES AND COVER CLOSED.
ANY REPLACEMENT FUSES MUST BE IGNITION PROTECTED
. COVER
MUST BE CLOSED IN EVERY OPERATIONAL CONDITION!
Environmental
Operating temperature
-40°C to 85°C
Storage temperature
-40°C to 125°C
Mechanical shock
SAE J2030 (RDEC2002), Section 6.16
Bombardment test
24 hour of dust, sand and gravel
Salt fog
96 hour period of salt fog per ASTM B117-94
Protection class
IP 66
Vibration
SAE J1455 (R2006), Section 4.10.4.2
Chemical resistance
Break fluid, AT fluid, antifreeze fluid, windshield
wash fluid, PS fluid and oil.
Electrical
Power supply voltage
12 V DC (8-16 V DC)
Dielectric voltage withstanding
80 V DC
Current consumption
1.5 mA battery quiescent current
Total current limit
200 A
Total current limit per connector
100 A
Overload
135%
Temperature rise
60°C
Insulation resistance
10 MOhm
Max load
Fuse channels 30 A at 12 V DC
Relay and fuse channels 20 A (resistive load)/16 A (inductive, motor, pump
load) at 12 V DC
Maximum board load
200 A
Power connector
2x M8 input studs, each rated at 100 A maximum
Power wire size
Calculated based on total board consumption
Output wire size
1.31 mm2 - 5.26 mm2 (#10-16 AWG)
Fuses
Mini blade fuse
Relays
280 footprint, 4 pin relay
Abnormal conditions
Revers polarity protection
- 24 V DC, SAE J1455 (RJUN2006) - duration of 5
minutes
Short circuit protection
Short to ground 5 minutes, ER455 (R2008) Section 5.10.4
Short to 16 V DC 5 minutes, ER455 (R2008) Section 5.10.4
Power up operation
Ramp battery voltage from 0 to minimum
operating voltage ad 1 V/ms, EP455 (R2008)
Section 5.10.7
5