background image

 
 
 

 
 
 

 

   
 
 
 
 

 
** The standard ACB in the catalog comes with D0, D0, U0, AX, and B 
options. 

 
 

 

 
 
 
 

 

 

 

Sunt Coil 

D0 Without Shunt coil 

D1 AC/DC 100V~130V 

D2 AC/DC 200V~250V 

D3 DC 125V 

D4 DC 24V~30V 

D5 DC 48V~60V 

D6 AC 380V~480V 

D7 AC 48V 

Closing coil  

D0 Without Closing coil 

D1 AC/DC 100V~130V 

D2 AC/DC 200V~250V 

D3 DC 125V 

D4 DC 24V~30V 

D5 DC 48V~60V 

D6 AC 380V~480V 

D7 AC 48V 

UVT Coil 

U0 Without UVT coil 

U1 AC/DC 100V~130V 

U2 AC/DC 200V~250V 

U3 DC 125V 

U4 DC 24V~30V 

U5 DC 48V~60V 

U6 AC 380V~480V 

U7 AC 48V 

Aux. contact & charging types 

AX Standard OFF-Charge 3a3b 

AC Standard ON-Charge 3a3b 

BX Standard OFF-Charge 5a5b 

BC Standard ON-Charge 5a5b 

HX High capacity OFF-Charge 5a5b 

HC High capacity ON-Charge 5a5b 

CC Standard ON-Charge 6a6b 

JC High capacity ON-Charge 6a6b 

GX High capacity OFF-Charge 3a3b 

GC High capacity ON-Charge 3a3b 

TX TCS OFF-Charge 4a4b 

TC TCS ON-Charge 5a5b 

AL Option 

AL Option 

AL AL1+MRB 

B B On/Off Button lock 

A1 AL1+MRB+RES (AC110~130V) 

M MI Mechanical interlock 

A2 AL1+AL2+MRB 

D Door Interlock or MOC 

A3 AL1+MRB+RES (DC110~125V) 

K K1 Keylock 

A4 AL1+MRB+RES (AC200~250V) 

K2 K2 Key Interlock set 

A5 AL1+MRB+Auto reset 

K3 K3 Key lock double 

A6 AL1+AL2+MRB+Auto reset 

R RCS Ready to close switch 

A7 AL1+MRB+RES (DC110~125V)+Auto reset 

T TM Temperature monitoring 

A8 AL1+MRB+RES (AC200~250V)+Auto reset 

H1 AC/DC 100~130V 

A9 AL1+MRB+RES (AC110~130V)+Auto reset 

H2 AC/DC 200~250V 

Y2 AL1+AL2+MRB (2b contact) 

H3 DC 125V 

Y6 AL1+AL2+MRB+Auto reset (2b contact) 

H4 DC 24~30V 

Z2 AL1+AL2+MRB (1a1b contact) 

H5 DC 48~60V 

Z6 AL1+AL2+MRB+Auto reset (1a1b contact) 

H6 AC 380~480V 

C C Counter 

H7 AC 48V 

S CS2 Charge switch communication 

  

Catalogue number:  

AN

□□□□□□ 

 

 

 

AS 

 
Air Circuit Breaker  1600-5000  70-85kA

 

 

 

 

AS

□□□□□□

 

Optional Configuration 

* AL- Trip Alarm 
  MRB- Manual Reset Button 
  RES- Remote reset switch 
  MOC- Mechanically Operated cell                               

Switch 

 

** Only 1 alarm trips options can be 
installed. 
    Only 1 key lock options can be 
installed. 
    Only 1 double shunt to be installed, 
and it cannot be used simultaneously 
with UVT. 
    MI cannot be used simultaneously 
with DI or MOC. 
     RCS and CS2 cannot be used 
simultaneously.

 

N.A.W. Controls Pty. Ltd. 

Telephone: (03) 9464 6555 

www.nawcontrols.com.au

 

LS ACB AS & AN range

 

June 2020 

Trip Unit Configuration 
  

 

AG5 
 
-  Protection:  Long  time,  Short  time,  Instantaneous,  ground  fault  and 
thermal. 
- Measurement of current on each phase. 
- Fault alarm for long time, short time, Instantaneous and ground faults. 
- Communication:  Modbus/RS-485 
 

 

    Profibus- DP 

- Power supply: self-power, work over 20% of the load current. (External 
power source required for comms). 
 

-AC/DC 100~250V 

 

-DC 24~60V 

- 10 fault recording stored 
- Operating buttons: Reset, Menu 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Eureka AN Series

Page 1: ...ion of protective coordination by ZSI A Configuration Fixed Type ACB Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Air Circuit Breaker 1 Trip relay 2 Counter 3 ON button 4 OFF button 5 Series name 6 Charge handle 7 Rated name plate 8 Charge Discharge indicator 9 ON OFF indicator 10 Corporation logo 11 Arc cover 12 Terminal cover 13 Cradle 14 Draw out handle 15 Position indicator ...

Page 2: ...inal cover 13 Cradle 14 Draw out handle 15 Position indicator 16 Handle storage space 17 Pad lock button 18 Arc chute 19 Control cover 20 Fixed type bracket 1 Terminal cover of control circuit 2 Cradle finger Line side 3 Cradle finger Load side 4 Draw out handle 5 Position indicator 6 Handle storage space 7 Pad lock button 8 Connecting conductor Line side 9 Connecting conductor Load side N A W Con...

Page 3: ...r supply terminal 4 Trip relay control terminal 5 Carrying grip 6 Trip coil or UVT coil 7 Mechanism 8 Main body 9 Counter 10 Trip coil 11 Closing coil 12 Motor Ass y 13 Aux switch 14 ON button 15 OFF button 16 MTD base 17 Trip relay 18 Front cover N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 4: ...ty kA Ics Icu 100 100 100 Rated making capacity kA peak IEC 60947 2 220V 230V 380V 415V 143 154 220 KS C 4620 AC 50 60Hz 460V 480V 500V 143 154 220 550V 600V 690V 105 143 187 Rated short time 1 sec 50 65 85 withstand current kA 2 sec 42 55 75 3 sec 36 55 65 Operating time ms Maximum total breaking time 40 Maximum closing time 80 Life cycle time Mechanical 10000 Electrical 2000 Main body Motor char...

Page 5: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range May 2020 Electrical Single Line Diagram ...

Page 6: ...h A7 AL1 MRB RES DC110 125V Auto reset T TM Temperature monitoring A8 AL1 MRB RES AC200 250V Auto reset H1 AC DC 100 130V A9 AL1 MRB RES AC110 130V Auto reset H2 AC DC 200 250V Y2 AL1 AL2 MRB 2b contact H3 DC 125V Y6 AL1 AL2 MRB Auto reset 2b contact H4 DC 24 30V Z2 AL1 AL2 MRB 1a1b contact H5 DC 48 60V Z6 AL1 AL2 MRB Auto reset 1a1b contact H6 AC 380 480V C C Counter H7 AC 48V S CS2 Charge switch...

Page 7: ...elay s tr 1 5 lr 12 5 25 50 100 200 300 400 500 Off Accuracy 15 or below tr 6 0 lr 0 5 1 2 4 8 12 16 20 Off 100ms tr 7 2 lr 0 34 0 69 1 38 2 7 5 5 8 3 11 13 8 Off Short Time Current setting A Isd Ir 1 5 2 3 4 5 6 8 10 Off Accuracy 10 Time delay s tsd I t Off 0 05 0 1 0 2 0 3 0 4 I t On 10 lr 0 1 0 2 0 3 0 4 I t Off Min Trip Time ms 20 80 160 260 360 Max Trip Time ms 80 140 240 340 440 Instantaneou...

Page 8: ...e last downstream device Instantaneous I Ii 1 Standard current setting knob Ii Setting range 2 3 4 6 8 10 12 15 Off In 2 Relay operates basing on the largest load current among the 3 phases 3 Total breaking time is below 50ms Long time delay L Iu Ir tr 1 Standard current setting knob Ir Setting range in N type and A type 0 4 1 0 In Iu 0 5 0 6 0 7 0 8 0 9 1 0 In Ir 0 8 0 83 0 85 0 88 0 9 0 93 0 95 ...

Page 9: ...UF_Pick up 55 1Hz 0 1Hz Under 60Hz 55Hz OF_Pick up 1Hz 0 1Hz frequency 50Hz 45Hz OF_Pick up 1Hz 0 1Hz 0 2 40sec 1 2 40sec 0 1sec 0 1sec Other protections Time delay s Pick up 1 2 40sec N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Ground Fault G Ig tg 1 Standard setting current knob ...

Page 10: ...controls com au LS ACB AS AN range June 2020 ZSI Zone Selective Interlocking A P S type 1 In case of that short time delay or ground fault accident occurs at ZSI built in system the breaker at accident site sends ZSI signal to halt upstream breaker s operation 2 To eliminate a breakdown trip relay of MCCB at accident site activates trip operation without time delay 3 The upstream breaker that rece...

Page 11: ...r AN AS Air Circuit Breaker 1600 5000 70 85kA AS Accessories Counter The Counter displays the total number of NO OFF operations performed on the ACB N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 12: ...ng button due to user s accidental handling It is not possible to perform ON OFF operation under the Button lock status Under Voltage Trip device UVT If the voltage of the main or the control power is under voltage UVT which is installed inside of the breaker breaks the circuit automatically Please connect with UVT time delay device to present the time delay function because UVT is technically an ...

Page 13: ...d the switch AL outputs the fault location MRB and AL can be operated only when tripping by an OCR To re close a circuit breaker after a trip press MRB to reset it for closing Trip alarm contact and MRB Manual reset bottom need to be purchased together Resistive load lamp load Inductive load A Motor load 8 VDC 11 3 6 3 30 VDC 10 3 6 3 125 VDC 0 6 0 1 0 6 0 1 250 VDC 0 3 0 05 0 3 0 05 250 VAC 11 1 ...

Page 14: ...temperature rises to an abnormal value the unit automatically sounds an alarm TRIO unit is installed on the cradle or the inside of panel LED Status DI1 Indicates digital Input 1condition DI2 Indicates digital Input 2condition DO ON Indicates temperature alarm output is ON DO OFF Indicates temperature alarm output is OFF 5 CB ON Indicates circuit break close condition CB OFF Indicates circuit brea...

Page 15: ...60V AC DC 100 130V AC DC 200 250V AC 380V AC 440 480V Load curent Max 5A 3A 1A 0 5A 0 3A 0 3A Starting current Max Load rpm Motor Charge time Dielectric strength Using temperature range Using humidity range Charge switch 10A at 250VAC 15000 19000 rpm Less than 5sec 2kV min 20 60 Max RH 80 No dew condensation 5 times of load current Type AN AS D AN AS E AS F AS G Endurance 20000 15000 10000 10000 N...

Page 16: ... AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS ...

Page 17: ... AS Characteristic Curve Short time delay S AS16D3 16H AS20D3 20H AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 18: ...aracteristic Curve Instantaneous I Ground fault G AS16D3 16H AS20D3 20H AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 19: ...gue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 06 16D Fixed unit AS16D3 16H Door Frame N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 20: ...e number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN 06 16D Draw out Unit AN16D3 16A Door Frame N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 21: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 20D Fixed Unit AS20D3 20H N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 22: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 20D Draw out Unit AS20D3 20A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 23: ...e number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN AS 20 35E Fixed Unit AN25E3 25H AS32E3 32H N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 24: ... number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN AS 20 35E Draw out Unit AN25E3 25A AN32E3 32A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range May 2020 ...

Page 25: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 40E Fixed Unit AS40E3 40V N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 26: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 40E Draw out Unit AS40E3 40A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Page 27: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 50F Draw out Unit AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Reviews: