background image

www.h-v-c.com

sales@h-v-c.com

Plate frame

S100 fire damper

Loden anchors
or equivalent fire
rated fixings

Concrete of
minimum thickness 150mm

Ductwork

Ductwork

DIRECTION OF AIRFLOW

Installation guide

Series 100 fire damper c/w plate frame

Upon receipt of unit - Before signing for the delivery

•  Flourescent yellow stickers are attached to every package we despatch detailing receipt 
  instructions and what to do if your goods are damaged.
•  The instructions on this must be followed or HVC will not be able to assist with any claims for 
  damage.

Prior to installation

•  If damper is to be stored on site, ensure it is stored in a clean and dry environment.
•  Immediately prior to fitment, remove all packaging from the unit. Take particular care inspecting 
  the inside of the unit for any packing materials which may disrupt damper operation.

Installation

•  Fire damper installation should only be carried out by competant persons. As life safety 
  devices, correct operation is reliant on correct installation.
•  Damper edges can be sharp. PPE should be used when handling.
•  Larger dampers can be very heavy, ensure suitable lifting methods are used to help prevent 
  injury.
•  There should be a minimum of 200mm of supporting construction between fire dampers 
  installed in separate ducts.

Installation guide: Series 100 fire damper c/w plate frame

Approved installation method, operation and installation declaration
Page 1 of 2 - Issue D - 26/02/2018

•  There should be a minimum of 75mm of supporting construction between the fire damper
  and any adjacent construction element, e.g. a corner or adjacent wall. 
•  Remove the safety cable tie around the fusible link. Failure to remove this will render the 
  damper inoperable.

Operation

•  Fusible link fire dampers are designed to operate without any command from an operator or 
  building maintenance system (unless equipped with an electromagnet or solenoid).
•  Fusible links will release at the temperature embossed onto the link body.
•  The use of electromagnets and solenoids enables the damper to be operated remotely, even 
  when the damper itself is not being exposed to elevated temperatures. 
•  The activation command may originate from an automated command or a human operator 
  through the building maintenance system.
•  Once the damper has been shut, it can only be opened by hand.
•  Once exposed to elevated temperatures/flames resulting in the damper closing, the damper 
  must be replaced.

Spares

•  A spare amount of replacement fusible links should be kept on site.

BS EN 13501-3:2005 + A1:2009

Classification report numbers: 

Galvanised units - P103718-1002/3

Stainless units - P103718-1002B/2

Multiple units - P103718-1002/2

I n s t a l l a t i o n   F D - 2 V P

D r y w a l l   p a r t i t i o n   i n s t a l l a t i o n

Installation procedure

•   Construct studwork aperture so that the space inside the steel 
  channels is 45mm larger than the overall size of the damper case. 
 

e.g. Damper case 500mm x 200mm, studwork aperture size 

  545mm x 245mm.

•  Clad one side of studwork with two layers of plasterboard. 

• 

Infill wall cavities with mineral wool.

•  Clad second side of studwork with two layers of plasterboard. 
•  Line aperture with one layer of plasterboard.
•  Offer damper into aperture and using 7.5mm thick spacers if 
  necessary to ensure correct positioning, affix damper into partition by 
  screwing through the plate frame and plasterboard into the steel 
  studwork
•  Screws to be 10mm in from outer edge of plate frame, and pitch to 
  be not more than 125mm. Ensure the screws gain a positive fix on 
  the steelwork.

Notes

•  The void at the non-access side of the damper does not require filling, 
  nor a pattress. 
•  No lugs are required when fitting this CE marked fire damper. 
•   Multiple assemblies are subject to the same installation. 
•   Air can flow through the damper in either direction. 

Material specifications 

Plasterboard:

 15mm thick and 30 minute fire rated

   

e.g. GTEC Fire Board, Knauf Fireshield, Gyproc Fireline

Mineral wool:

  Rockwool RW5, Knauf RS100 or equivalent

I n s t a l l a t i o n   F D - 2 V M

M a s o n r y   w a l l   i n s t a l l a t i o n

Installation procedure

•   Construct wall so that the aperture for the fire damper is 15mm larger 
  than overall size of the damper case. 
 

e.g. Damper case 500mm x 200mm, wall aperture size 515mm x 

 215mm.

•   Offer damper into aperture and using 7.5mm thick spacers if 
  necessary to ensure correct positioning, affix damper into partition by 
  screwing through the plate frame into the wall. 
•   Screws to be 10mm in from outer edge of plate frame, and pitch to 
  be not more than 125mm. Ensure the screws gain a positive fix on 
  the concrete/masonry.

Notes

•   The void at the non-access side of the dampers does not require 
  filling, nor a pattress.
•   No lugs are required when fitting this CE marked fire damper. 
•   Multiple assemblies are subject to the same installation. 
•   Air can flow through the damper in either direction. 

I n s t a l l a t i o n   F D - 2 H C

C o n c r e t e   f l o o r   i n s t a l l a t i o n

Installation procedure

•   Construct floor so that the aperture for the fire damper is 15mm larger 
  than overall size of damper case. 
 

e.g. Damper case 500mm x 200mm, floor aperture size 

  515mm x 215mm.

•   Offer damper into aperture and using 7.5mm thick spacers if 
  necessary to ensure correct positioning, affix damper into partition 
  using fixings as detailed below, through the plate frame into the floor.
•   Fixings to be 10mm in from outer edge of plate frame, and pitch to 
  be not more than 125mm. Ensure the fixings gain a positive fix on 
  the concrete/masonry.

Notes

•   The void at the non-access side of the dampers does not require filling, 
  nor a pattress. 
•   Air must flow towards the lock guides - See arrow below. 

Material specifications 

Floor:

 

150mm (minimum) thick concrete.

Fixings:

  Loden anchors, 5mm diameter x 50mm long

   

Equivalent fixing acceptable

Plate frame

S100 fire damper

Ductwork

Concrete/masonry wall

BS EN 13501-3:2005 + A1:2009

Classification report numbers: 

Galvanised units - P103718-1002/3

Stainless units - P103718-1002B/2

Multiple units - P103718-1002/2

BS EN 13501-3:2005 + A1:2009

Classification report numbers: 

P101275-1001/1

IMPORTANT NOTE

It is a legal requirement that fire dampers are installed in the way instructed by the manufacturer. 

Any other installation is untested and therefore illegal. 

Responsibility for ensuring correct installation lies with all parties in the supply chain. 

Plate frame

S100 fire damper

2 x 15mm plasterboard sheets
each side of steel stud

Mineral wool infill
in wall cavities

Steel studs creating
aperture frame

15mm plasterboard lining aperture

fixed with appropriate fixings to
steelwork at pitch of not more than 300mm

Ductwork

Reviews: