SPECIFICATIONS CHART - 1000 SERIES
DIMENSIONAL DRAWING NCHP-018-1019, NCHP-024-1019, NCHP-030-1019
8
19 7/8"
7/8" K.O.
25 3/4"
1 3/8" K.O.
(2)
7/8"
(2)
1 1/2"
1 1/8"
2 7/8"
8 1/2"
10 7/8"
13 5/8"
1 9/16"
4 31/32"
7/8" (2)
2 19/32"
15/16"
2 3/32"
1 17/32"
1 17/32"
3 17/32"
15/16"
1 3/8" (2)
1000 SERIES HEAT PUMP
28 5/8"
18 1/2"
MODEL NO.
NCHP-018
NCHP-024
NCHP-030
DIMENSIONS
26”
28 1/2”
18 1/2”
3/8”
5/8”
3/4”
26”
28 1/2”
18 1/2”
3/8”
3/4”
3/4”
26”
28 5/8”
18 1/2”
3/8”
3/4”
3/4”
Width
Height
Length
Liquid Valve
Vapor Valve
Drain Connection MPT
CAP. COOLING
18,000
24,000
28,500
CAP. HEATING 47°F
17,000
22,500
26,000
ELECTRICAL
208/230
60
1
12
14.6
25
208/230
60
1
12
17.7
30
208/230
60
1
12
19.8
30
Volts
Hertz
Phase
Min. AWG Wire
Min. Cir. Ampacity
Max. Fuse
COMPRESSOR
7.0
41
9.9
61
10.7
61
RLA (Amps)
LRA (Amps)
FAN MOTOR
0.25
1140
1.2
0.25
1140
1.2
0.50
1575
2.8
HP
RPM
Amps (Full Load)
COIL
3.46
16
3.46
16
3.46
16
Face Area
FPI
Service Clearance........30”