background image

Installation

23

NCR 4072 UPS Site Preparation, Installation, and Operation Manual

S

05147374 Rev C

Uncontrolled Copy

Network Transient

Protector

Two 5-15 Receptacles

Four 5-15 Receptacles

6-ft Power Cord

with 5-15 Plug

Fan

Communication Port

DIP Switches

Site Wiring Fault

Indicator

USB Port

Input Overcurrent

Protector

Figure 11. 1000 VA, 120V Rear Panel

Six 5-15 Receptacles

6-ft Power Cord

with 5-15 Plug

Network Transient

Protector

Fan

Communication Port

DIP Switches

Site Wiring Fault

Indicator

USB Port

Input Overcurrent

Protector

Figure 12. 1400 VA, 120V Rear Panel

Summary of Contents for 4072

Page 1: ...NCR 4072 500 1400 VA Uninterruptible Power Systems UPS Site Preparation Installation and Operation Manual...

Page 2: ...be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase...

Page 3: ...rective on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Dir...

Page 4: ...ur operator s manual for additional information such as important operating and maintenance instructions SAFETY EARTHING TERMINAL Indicates the primary safety ground LOAD ON OFF Press the button with...

Page 5: ...Rear Panels 22 4 Operation 27 Turning the UPS On 27 Starting the UPS on Battery 27 Turning the UPS Off 27 Standby Mode 28 UPS Front Panel 28 Initiating the Self Test 28 5 Additional UPS Features 29 V...

Page 6: ...ration Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy 7 Specifications 39 8 Troubleshooting 43 Audible Alarms and UPS Conditions 43 Silencing an Audible Alarm 44 Site Wiring Faul...

Page 7: ...when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost produ...

Page 8: ...sures consistent voltage to your load by correcting voltage fluctuations Hot swappable batteries simplify maintenance by allowing you to replace batteries safely without powering down the critical loa...

Page 9: ...ted to an AC supply For 220 240V models the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the...

Page 10: ...r other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Disconnect charging source prior to connecting or disconnecting battery terminals Prope...

Page 11: ...rolleret indend rsmilj frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk st d Rumtemperaturen m ikke overstige 40 C UPS en b r ikke betjenes n r vand eller h j fugt...

Page 12: ...e kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur en vochtigheidregeling te worden ge nstalleerd waar geen geleidende verontreinigingen aanwezig zijn De...

Page 13: ...palon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell ve...

Page 14: ...ler l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas ut...

Page 15: ...llierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser ode...

Page 16: ...Safety Warnings 10 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy UPS UPS UPS UPS AC UPS UPS UPS UPS 40 C UPS 95 UPS 1 5 mA...

Page 17: ...disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Per ridurre il rischio di incendio o di scossa elettrica installare il gru...

Page 18: ...som er forbundet med den For redusere fare for brann eller elektriske st t b r denne UPS en installeres i et innend rs milj med kontrollert temperatur og luftfuktighet som er fritt for ledende foruren...

Page 19: ...uzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condut veis A temperatura ambiente n o deve exceder 40...

Page 20: ...Safety Warnings 14 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy 40 95 1 5...

Page 21: ...dio o de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cer...

Page 22: ...en Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande...

Page 23: ...rials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or conceal...

Page 24: ...ernal Battery Connection Use the following procedure to ensure proper battery operation before installing the UPS 1 Verify that the UPS is off and unplugged 2 Remove the UPS front panel Figure 2 Remov...

Page 25: ...al battery connector Figure 4 Removing the Protective Label 5 Connect the red wire to the battery connector NOTE A small amount of arcing may occur when connecting the batteries This is normal and doe...

Page 26: ...llowing steps explain how to install the UPS Figure 8 shows a typical installation only See UPS Rear Panels on page 22 for the rear panel of each model 1 If you are installing power management softwar...

Page 27: ...s or 10A for 230V models 4 Plug the equipment to be protected into the UPS output receptacles NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of th...

Page 28: ...rt Four 5 15 Receptacles 6 ft Power Cord with 5 15 Plug DIP Switches Network Transient Protector Site Wiring Fault Indicator USB Port Input Overcurrent Protector Figure 9 500 VA 120V Rear Panel Four 5...

Page 29: ...es 6 ft Power Cord with 5 15 Plug Fan Communication Port DIP Switches Site Wiring Fault Indicator USB Port Input Overcurrent Protector Figure 11 1000 VA 120V Rear Panel Six 5 15 Receptacles 6 ft Power...

Page 30: ...munication Port Four 10A IEC 320 Receptacles DIP Switches Network Transient Protector 10A IEC 320 Input Connector USB Port Figure 13 500 VA 230V Rear Panel Four 10A IEC 320 Receptacles DIP Switches Ne...

Page 31: ...ptacles Four 10A IEC 320 Receptacles 10A IEC 320 Input Connector Fan DIP Switches Network Transient Protector Communication Port USB Port Figure 15 1000 VA 230V Rear Panel Six 10A IEC 320 Receptacles...

Page 32: ...Installation 26 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Page 33: ...test and enters Normal mode The indicator illuminates indicating that power is available from the UPS output receptacles Starting the UPS on Battery NOTE The UPS does not auto detect the input freque...

Page 34: ...l indicates the UPS status and also identifies potential power problems Figure 17 shows the UPS front panel indicators and controls On Off Button Test Alarm Reset Button Power On Indicator Green On Ba...

Page 35: ...rear panel of each unit see Figure 18 are used to configure the output voltage and input voltage range 1 The UPS must be completely shutdown To turn off the UPS press and hold the button for two seco...

Page 36: ...V 216V 254V ON ON Default position Communication Options The UPS is equipped with a USB and a DB 9 communication port Either the USB port or the DB 9 communication port may be used to monitor the UPS...

Page 37: ...nitiates the saving of all data and an orderly shutdown of the equipment The cable pins are identified in Figure 20 and the pin functions are described in Table 2 3 8 7 9 1 6 2 4 5 UPS Rear Panel Figu...

Page 38: ...ector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange en...

Page 39: ...ient temperature of 25 C 77 F NOTE If the UPS requires any type of transportation in the future disconnect the UPS internal battery connector using the steps in UPS Internal Battery Connection on page...

Page 40: ...ing batteries W A R N I N G Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal...

Page 41: ...Operation Manual S 05147374 Rev C Uncontrolled Copy 2 Slide up and remove the metal battery cover 1400 VA 500 1000 VA 3 500 VA models Disconnect the red battery cable and then disconnect the black bat...

Page 42: ...ttery cable and then pull the battery out onto a flat stable surface Disconnect the black battery cable to the UPS as shown 750 1000 VA 5 1400 VA models Disconnect the red battery cable and then pull...

Page 43: ...tteries to charge for 6 to 24 hours before testing Press and hold the button for three seconds to initiate a self test The 15 second test automatically distributes the load to the batteries and tests...

Page 44: ...attery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements Do not open or mutilate the battery or batteries Releas...

Page 45: ...Dimensions WxHxD 500 VA 15 0 x 19 3 x 27 0 cm 5 9 x 7 6 x 10 6 750 1000 VA 15 0 x 19 3 x 33 5 cm 5 9 x 7 6 x 13 2 1400 VA 15 0 x 19 3 x 39 0 cm 5 9 x 7 6 x 15 4 UPS Weights 500 VA 7 8 kg 17 2 lb 750 V...

Page 46: ...utput Receptacles 500 750 VA 4 5 15 1000 1400 VA 6 5 15 500 750 VA 4 10A IEC 320 1000 1400 VA 6 10A IEC 320 Table 6 Environmental and Safety 120V Models 230V Models Operating Temperature Up to 1 500 m...

Page 47: ...ree valve regulated lead acid Charging Advanced charging for faster recovery approximately 3 hours to 90 usable capacity at nominal line and no supplementary power supply load Monitoring Advanced moni...

Page 48: ...Specifications 42 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Page 49: ...lt on 120V models Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 9 to determine and resolve the UPS alarm...

Page 50: ...ession Table 9 Troubleshooting Alarm or Condition Possible Cause Action The indicator is not on the UPS does not start The power cord is not connected correctly Check the power cord connections the UP...

Page 51: ...rected or the battery is completely discharged If the condition persists the input voltage in your area may differ from the UPS nominal Change the UPS input voltage to match your local voltage see Vol...

Page 52: ...ork and turn off your equipment Turn off the UPS Contact Customer Service 3 beeps every 10 seconds Failed attempt to start the UPS on battery Plug the UPS into a power outlet for 24 hours to charge th...

Page 53: ...blem Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on t...

Page 54: ...imitations IF YOU ARE A CONSUMER UNDER APPLICABLE LAW ALL EXPRESS AND IMPLIED WARRANTIES INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY AN UNWRITTEN WARRANTY THAT THE PRODUCT...

Page 55: ...sign The repair or replacement will be warranted for 90 days or the remainder of the original warranty period whichever is longer This limited warranty is the only one we give on your NCR product and...

Page 56: ...Troubleshooting 50 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Reviews: