A E - 1 5 0 s y s t e m – U s e r M a n u a l
14
Installation on the transformer tank wall
Install the AE-150 on a wall of the transformer tank. Its location must be
measured from the tank origin point to the center of the AE-150 instrument
(middle of the indicator cross). Keep the values for later as they will be used in
Mirador Tx software. These measurements are crucial and need to be taken
with great precision. Refer to next figure.
The AE-150 magnets are very strong. Be careful not to pinch any
fingers, hair or any other body part while installing the AE-150. Keep
the AE-150 away from any object made of ferromagnetic materials at
all time.
Once the AE-150 is installed on the transformer tank, press all four sensors to
maximise acoustic couplant contact. Any air bubble or debris between the
surface of the sensor and the transformer tank material may result in poor
acoustic measurement. Refer to next figure.