Setting Up Your Server 3-5
Do not install the rack in the places listed below. Installing the rack or mounting the server on the
rack in such a place may cause some malfunction to occur.
Do Not:
Locate a rack in a narrow space that would inhibit devices from being pulled out from the
rack completely.
Locate the rack on a floor that cannot bear the total weight of the rack and devices
mounted in the rack.
Locate the rack in a place where stabilizers cannot be installed or where the rack can be
installed only after proper earthquake-resistant is constructed.
Locate the rack on an uneven or slanting floor
Locate the rack in an area that has drastic temperature change (near a heater, air
conditioner, or refrigerator).
Locate the rack where intense vibration may be generated.
Locate the rack where corrosive gas is generated (ex. the area, where the vapor of sulphur
is generated), chemicals are nearby, or chemicals may be sprayed accidentally.
Place the rack on a carpet not subject to the anti-static process.
Locate the rack where some objects may fall on the rack.
Locate the rack near a device that is generating intense magnetic fields (such as a TV,
radio, broadcast/communication antenna, power transmission wire, and electromagnetic
crane.) If unavoidable, contact your service representative to request proper shielding.)
Locate the rack where the power cord of the server must be connected to an AC outlet that
shares other devices with large power consumption.
Locate the rack next to equipment that generates power noise (e.g., contact spark at
power-on/power-off of commercial power supply through a relay). If you must install
the server close to such equipment, request your service representative for separate power
cabling or noise filter installation.
Locate the rack where following conditions can not be satisfied.
Conditions for operation: *
Temperature: 10 to 35
°
C
Humidity: 20 to 80% (no condensation)
* It is recommended that the server should be used in a room where temperature is in the
range between 15 to 25
°
C.
* If installed in a closed or multi-unit rack assembly, required air flow for cooling might
not be maintained, and this cause the operating ambient temperature of the rack
environment may rise greater than room ambient. Therefore, consideration should be
given to installing the server in an environment compatible with the rated ambient
temperature (10 to 35
°
C) and appropriate air flow.
Summary of Contents for N8100-1220F
Page 7: ......
Page 8: ......
Page 9: ......
Page 38: ...1 18 Notes on Using Your Server This page is intentionally left blank...
Page 76: ...2 38 General Description This page is intentionally left blank...
Page 187: ...Configuring Your Server 4 83 3 Setting menu for VD 0 is displayed...
Page 494: ...F 4 Product Configuration Record Table This page is intentionally left blank...