8
4.
MASONRY INSTALLATION
NOTE: Receiver for fan remote control must be fitted before
installing the appliance. Refer to section 3.6 Fitting Receiver
for Remote Control for more detail.
Refer to this section for clearance requirements and
instructions if the heater is to be in a masonry installation.
4.1.
CLEARANCES TO COMBUSTIBLE MATERIALS
The dimensions given in the table and image below represent
the minimum clearance (in millimetres) to combustible
materials, such as a mantelpiece with columns, when installed
in a non-combustible fireplace.
Description
Clearance
A (Width between mantelpiece columns)
1335
B (Height to mantelpiece from hearth)
1400
C (Height to mantelpiece from appliance)
750
D (Distance to side wall)
550
Note – mantelpiece clearance can be reduced by installing a
heat shield beneath it in accordance with AS/NZS 2918.
4.2.
FLOOR PROTECTOR (HEARTH)
The minimum dimensions and construction materials for the
floor protector when installed in a masonry fireplace are the
same as for a Built-In installation. Refer to section 3.4 Floor
Protector (Hearth) for details.
4.3.
INSTALLING THE FLUE
If the appliance is installed in a masonry fireplace with
masonry chimney, the flue must be installed in accordance
with AS/NZS 2918.
If the chimney is not masonry and is constructed wholly or
partly from combustible material, it must be installed with the
manufacturer-supplied Built-In flue kit.
Any gaps between the 8 inch active flue and the flue spigot on
the appliance should be filled with either stove cement
designed for this purpose or high temperature cloth tape.