44
Appendix D Error codes
Code
Module
Type
Error cause
User recommended action
S002-S
SOLAR
SOFT
Over temp Solar Check ambient temperature of
PowerRouter. Check for ob-
structions in the air flow chan-
nel.
S004-S
SOLAR
SOFT
Solar panel volt-
age too high
Check solar panel configuration
and wiring.
S005-S
SOLAR
SOFT
Boostvoltage
intermediate bus
too high
Contact your dealer if this fault
occurs frequently
S007-S
SOLAR
SOFT
Solar Current too
high
Check solar panel configuration
and wiring.
S013-S
SOLAR
SOFT
Solar panel pow-
er output is to
high
Contact your dealer if this fault
occurs frequently
S016-S
SOLAR
SOFT
Internal com-
munication
error
Contact your dealer if this fault
occurs frequently
D001-S
DCAC
SOFT
Over temp AC
Check ambient temperature of
PowerRouter. Check for ob-
structions in the air flow chan-
nel.
D002-S
DCAC
SOFT
Bus overvoltage
Contact your dealer if this fault
occurs frequently
D003-S
DCAC
SOFT
Bus undervoltage Contact your dealer if this fault
occurs frequently
D007-S
DCAC
SOFT
grid relay failure Contact your dealer if this fault
occurs frequently
D010-S
DCAC
SOFT
Inverter current
overload
Check load configuration Con-
tact your dealer if this fault
occurs frequently
D011-S
DCAC
SOFT
AC line out un-
dervoltage
Check grid or generator volt-
age
D012-S
DCAC
SOFT
AC line out over-
voltage
Check grid or generator volt-
age
D015-S
DCAC
SOFT
Internal com-
munication
error
Contact your dealer if this fault
occurs frequently
D023-H
DCAC
HARD
current overload Disconnect exesive loads
Summary of Contents for PowerRouter PR50S
Page 1: ...PowerRouter installation and operatingmanual Solar 5kW 3 7kW 3kW English...
Page 2: ......
Page 56: ...56 Notes...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 62: ...62...
Page 63: ...63 the PowerRouter you re in charge E welcome PowerRouter com I www PowerRouter com...
Page 64: ...64 your installer Manual part no 5277337 A 01 the PowerRouter you re in charge...