WIM | INSTALLATION GUIDE
Connections
5/20
3
CONNECTIONS
Below the connections are shown which are available on front panel of the device.
Shielded cable shall be used for all connections except power supply.
Figure 2: Front view
RS485
Connect the RS485 to the License Plate Reader (9600, 8N1).
A:
RS485-A (yellow)
B:
RS485-B (green)
GND:
RS485-GND (purple)
WIEGAND
Connect the Wiegand output to your access control system.
D1:
Wiegand data-1 (white)
D0:
Wiegand data-0 (green)
GND:
Ground (black)
MAGSTRIPE
Magstripe Clock and Data output.
Select with the plate conversion mode switches. See for more
details chapter 5.
D1:
Data
D0:
Clock
CLS:
Card Loaded
GND:
Ground
BARCODE
Barcode wand emulation data output in code39 format.
Select with the plate conversion mode switches. See for more
details chapter 5.
D1:
Wand emulation data output (black=high)
D0:
Wand emulation data output (black=low)
GND:
Ground
STS LED
Status LED (green)
Blinks regularly to indicate standby.
Blinks fast to indicate that a RS485 message (license plate) is
processed.
ERR LED
Error LED (red)
Normally off.
On if match-list used and license plate not found.
LAN
The LAN connection (RJ45 socket) is used to configure the
device and manage the match-list.
Link LED (left):
Off=No link, Amber=10Mbps,
Green=100Mbps.
Activity LED (right):
Off=No activity, Amber=HDX
Activity, Green=FDX Activity.
RS485
connection
WIEGAND
output
LED
indications
LAN
connection
G
ND
CL
S
D0
D1
G
ND
A
B