NCF
EN
18
NCF 30/15
NCF 30/20
NCF 30/25
NCF 40/25
NCF 50/25
NCF 80/20 NCF 120/15 NCF 120/25 NCF 160/25
Total pressure
(in w.g.)
7.9 - 2.3
11.6 - 3.8
in w.g
10.2 - 3.5
14.6 - 5.3
18.2 - 6.3
12.7 - 4.1
14.4 - 4.7
21.1 - 6.8
20.3 - 7.5
Motor power
(hp)
3.0 hp
4.0 hp
5.5 hp
7.5 hp
7.5 hp
10 hp
15 hp
20 hp
25 hp
Speed (r/min)
3500 r/min
3515 r/min
3535 r/min
3510 r/min
3520 r/min
3550 r/min
3540 r/min
3550 r/min
3560 r/min
Voltage (V)
Current (A)
208
8.6
208
11.5
208
15.1
208
18.7
208
18.7
208
26.2
208
38.4
208
52
208
66.4
Voltage (V)
Current (A)
230YY/460Y
7.8/3.9
230YY/460Y
10.4/5.2
230ΔΔ/460Δ
13.6/6.8
230ΔΔ/460Δ
17/8.5
230ΔΔ/460Δ
17/8.5
230ΔΔ/460Δ
23.8/11.9
230ΔΔ/460Δ
34.8/17.4
230ΔΔ/460Δ
46.8/23.4
230ΔΔ/460Δ
60/30
Voltage (V)
Current (A)
575 V
3.1 A
575 V
4.2 A
575 V
5.5 A
575 V
6.8 A
575 V
6.8 A
575 V
9.5 A
575 V
11.0 A
575 V
19.4 A
575 V
24 A
Phase
3 phase
3 phase
3 phase
3 phase
3 phase
3 phase
3 phase
3 phase
3 phase
Starting
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
Protection
IP 55
IP 55
IP 55
IP 55
IP 55
IP 55
IP 55
IP 55
IP 55
Weight (lbs)
148
187
231
243
247
331
355
511
644
Working
temperature (°F)
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Maximum
+ 140
Ambient
temperature (°F)
-22 to +104 -22 to +104 -22 to +104 -22 to +104 -22 to +104 -22 to +104 -22 to +104 -22 to +104 -22 to +104
Sound power
level Lw(A) ±
3dB *
94dB(A)
103dB(A)
97dB(A)
106dB(A)
106dB(A)
98dB(A)
104dB(A)
107dB(A)
103dB(A)
Sound pressure
level Lp(A) ±
3dB *
80dB(A)
89dB(A)
82dB(A)
83dB(A)
86dB(A)
83dB(A)
89dB(A)
92dB(A)
90dB(A)
*Reference standards: ISO 3744, ISO 3746, ISO 13347. Installation Type D: ducted inlet, ducted outlet.
4
Installation
WARNING!
Risk of personal injury.
•
All installation and assembly operations must be carried out only by qualified personnel,
equipped with the correct PPE for protection against blows and/or falling objects.
•
Before installation, the user must provide a well-levelled fixing surface. Incorrect
levelling may cause abnormal fan vibrations that over time could cause deformation
and/or breakage, with the detachment of fan parts, representing a hazard for exposed
persons that may even be fatal.
•
All guards installed must remain correctly connected to the fan with all relative fasteners
(bolts, nuts, etc). The removal of one or more fixing points may impair the functionality
and solid fixing of the guard.
•
Fans supplied as standard versions are not intended for use in potentially explosive
environments.
•
The safety measures adopted for using the fan must also be tailored to suit the specific
applications for which the fan will be used. The safety measures taken differ depending
on the type of fan installation. Therefore, the information in this manual is indispensable
for the appropriate and hazard-free use of the fan.