Fan Inverter
10.2.2 Protections
The parameter P1.4 Motor nominal current acts as the ‘set point’ for the overload protection, together with oth-
er parameters in P3.9.
The parameter P1.7 Motor current limit determines the maximum current supplied to the motor from the fre-
quency converter and is set by default to the rating of the Fan Inverter.
The parameter P3.9.11 MotorStall flt protects the motor in case the fan impeller is locked or the motor has not
reached the ‘Frequency limit’ within the ‘Stall time limit’ and still current higher than ‘Stall current’.
Additional protection can be utilized by PTC thermistor in the motor and the accessory STO and ATEX(PTC)
board OPTBJ.
10.3 Change display language
Note
The only languages that can be selected depend on the language pack that came with Fan Inverter.
See
. Change the display language as follows:
1
Press the BACK/RESET button, to go to ‘Main menu’, see
2
Select ‘Quick Setup’ and press the OK button.
3
Select ‘Startup Wizard’ and press the OK button.
4
Select ‘Edit’ and press the OK button.
5
Select ‘Activate’ and press the OK button.
6
Select the language and press the OK button.
7
Press the BACK/RESET button repeatedly to get back to ‘Main menu’.
10.4 Change real time clock
Note
The real time clock is set as the normal time. If daylight savings is selected during daylight savings time,
set the clock one hour earlier than the present time. When the OK button is pushed to change the time,
the clock will jump one hour ahead.
See
. Change the real time clock as follows:
1
Press the BACK/RESET button, to go to ‘Main menu’, see
. Select ‘Quick Setup’ and press the OK but-
ton.
2
Select ‘Startup Wizard’ and press the OK button.
3
Select ‘Edit’ and press the OK button.
4
Select ‘Activate’ and press the OK button.
5
Select the language and press the OK button.
6
Select the ‘Daylight saving’ and press the OK button.
7
Use the arrows to change the time and press the OK button.
8
Press the BACK/RESET button repeatedly to get back to ‘Main menu’.
10.5 Commissioning
Commissioning must be done according to Section ‘Commissioning’ in the VACON 100 Installation Manual.
10.6 Favourites
See
. To make a menu item available for viewing and editing in Monitor mode that is normally only
available in Normal mode, certain menu items can be added to ‘Favourites’ in the following way:
1
Press the BACK/RESET button, to go to ‘Main menu’, see
2
Select the menu item and press the OK button.
3
Select ‘Add to favourites’ and press the OK button.
If a menu item has been saved to ‘Favourites’,it can be accessed by selecting ‘Favourites’ and press OK. Press
BACK/RESET repeatedly to get back to ‘Main menu’. For more information see the VACON 100 HVAC Application
Manual and section ‘Change user level with default access code’.
24