FlexPAK 800/1000
31
EN
4.2.31 VacLoTm
Delay Timer for “Warning! Low Vacuum”, see section
‘3.2.5 Warning Low Vacuum’
and
section
‘4.2.28 Vac_Low’
.
This timer delays showing the message “Warning! Low Vacuum “ when the vacuum is too
low in the system. The timer serves as a filter to remove short-term vacuum variations in
the system. When the timer expires, the message “Warning! Low Vacuum “ is displayed.
ESC
OK
VacLoTm
1/1
T = 01:00m
Ta = 00:00m
T = 01: 00m default setting 1 minute delay
Ta = 00: 00m shows the lukewarm delay time
4.2.32 PSIFC
Menu for activating Pilot Signal Interlock Filter Cleaning (PSIFC). Filter cleaning does not
take place until the pilot signal has disappeared and DIR_Time has expired.
If AEB-TVFD is set to ‘On’ , in other words, AEB-Flap Valve opening is chosen, the bin
emptying sequence is also interlocked when there is a pilot signal to the unit.
ESC
OK
PSIFC
1/1
Switch = Off
4.2.33 PresepTm
Menu for AEB-Flap Valve, simple TVFD and Preseparator opening cycle settings. The values
for ‘TL’ and ‘TH’ depend on which function is being used. See Section
‘5 Automatic bin
emptying function’.
ESC
OK
PresepTm
1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TH= See Section
‘5 Automatic bin emptying function’
.
TL= See Section
‘5 Automatic bin emptying function’
.
4.2.34 FlushTmr
Menu for automatic flushing of the duct system with the interval timer. FlushTmr activates
FlushCy1 and FlushCy2. FlushTmr is deactivated if PSCFlush is activated ‘Switch=On’, see
Section
‘4.2.18 PSCFlush’.
ESC
OK
FlushTmr
1/1
T = 30:00m
Ta = 00:00m