FlexPAK 800/1000
37
EN
If there are multiple indicator lamps connected to the system, it is recommended that
semiconductor LED indicators used.
7
Pneumatic filter cleaning valve
7.1
Filter cleaning button
The filter cleaning button will only work when the system is in Standby mode or Running
mode.
7.2
Filter cleaning in Standby mode
Perform a filter cleaning in Standby mode as follows:
1.
From Off mode, put the unit into Standby mode by pressing the Standby/Running
button.
2.
Start filter cleaning by pressing the filter cleaning button.
The unit goes into Running mode, the motor starts and the FCV closes and vacuum is
established in the system. The unit will now open and close the FCV once and then leave
the FCV in its open position. After the cleaning cycle, the unit goes into Idling mode. The
unit waits for a pilot signal for 10 minutes. If the pilot signal is not received during this time,
the unit will stop its motor and go into Standby mode.
To perform a new filter cleaning in Idling mode, activate the pilot signal and enter Running
mode, or toggle the Standby/Running button to go to Standby mode and press the filter
cleaning button again.
7.3
Filter cleaning in Running mode
Perform filter cleaning in Running mode as follows:
1.
Put the system into Standby mode by pressing the Standby/Running button.
2.
Activate the pilot signal by connecting terminals X1:13 and X1:14 with a jumper.
The unit goes into Running mode. The motor starts, the FCV closes and pressure is
established in the system.
3.
Start the filter cleaning by pressing the filter cleaning button.
The unit will now open and close the FCV 3 times and then leave the FCV in its closed
position. After the last cleaning cycle, the unit returns to Running mode and waits for the
pilot signal to stop. It is possible to perform multiple filter cleaning cycles in Running mode.
When the pilot signal stops, the unit runs for 10 seconds (DIR time) and then opens the FCV
and goes into idling mode. The unit waits for a pilot signal for 12 minutes. If the pilot signal
is not received during this time, the unit will stop the motor and go into Standby mode.
The idling time is set by the SSR timer and default is 12 minutes. DIR time is the delay after
the pilot signal has stopped before opening the FCV. The default is 10 seconds.
7.4
Filter cleaning valve function
The PLC output DO3 is set and sends +24 V to the solenoid valve. The solenoid valve opens
the air flow to the pneumatic piston, which moves the lid on top of the filter upwards
letting in air with atmospheric pressure to the filter top. This sudden opening of the lid on
the top lets in air with great speed which creates a sudden pressure rise above the filters.
The pressure increase blows air through the filter bags removing the dust from the filters.
When power to the solenoid valve disappears, the valve closes and evacuates the
pneumatic piston. The lid falls down and closes the opening of the filter top.