FlexPAK DX
If the dust is abrasive, it may be necessary to use
thick-walled (or rubber-coated) material in bends and
other exposed areas.
To avoid pressure losses, the duct system is to be
as short as possible and designed with two or more
branches. Use larger diameters on the clean side to re-
duce pressure losses.
5.4 Installing the unit
WARNING! Risk of personal injury
Always stop the unit before looking into the
outlet. The fan rotates at high speed and debris
and particles coming out of the outlet may
cause eye injury.
For suppression units, detailed information re-
garding the installation of an explosion sup-
pression system can be found in the suppres-
sion system manual. Work is only to be carried
out by certified personnel.
To minimize any secondary explosion damage
and spread of fire, the proper documentation
and checklists of how to handle a fire in the
unit have to be developed. Such documents are
to be developed in co-operation with the local
fire authorities and take into account the prop-
erties of the collected material.
5.4.1 Indoor installation
CAUTION! Risk of equipment damage
If the exhaust air duct is blocked, the unit may
create an overpressure, that may cause major
damage to the heat exchanger.
Never completely seal a small room with the
unit installed.
Ensure that the room where the unit is in-
stalled is well ventilated.
It is recommended that the unit is positioned indoors.
Under some conditions, the unit may draw air directly
into the high-pressure fan. This may cause a dan-
gerous underpressure in the room if air cannot enter
freely. There are to be two openings for ventilation,
at least 250×250 mm (10"×10") in size. One is to be
placed up high and the other one down low.
The warm exhaust air is to be directed from the unit
, item 4. Connect
a duct that directs the exhaust air outdoors.
The air can be directed to a heat exchanger, but there
are not to be any dampers that may obstruct the air
flow.
5.4.2 Outdoor installation
If installed outdoors, consider the following:
• The area needs to be protected from the weather.
Cover the top of the unit to protect it from snow,
rain or falling debris.
• Install a lightning conductor, see
• Environmental and ambient conditions. See
.
5.4.3 Moving the unit
WARNING! Risk of personal injury
• Use proper lifting and protective equipment.
• Be careful not to let the unit tip over to avoid
a crushing risk.
• The unit is to be anchored to the floor, par-
ticularly if it is located at a high level, to en-
sure that it does not move and fall down. The
frame has four holes for anchoring. Take care
during relocation and transport of the unit to
avoid tipping. If the unit is to be moved, the
frame is to be attached to the front of the
, item 1. Before
moving the unit ensure that it is emptied of
extracted materials.
5.5 Electrical installation
WARNING! Risk of electric shock
• Work with electric equipment is to be carried
out by a qualified electrician.
• The connected wiring system is to be elec-
trically connected to the Potential Equalizing
System (PES) on the premises.
The electrical connection is NOT to be
equipped with an earth leakage circuit breaker
when the frequency converter is provided with
an EMC filter. The EMC filter function will make
the earth leakage circuit breaker shut off the
power.
Following the European standard, the incom-
ing 3-phase supply is to be fitted with a hand-
operated disconnecting device that conforms
to the demands of disconnectors. The discon-
necting device is to be fitted within 2–3 m from
FlexPAK DX and be clearly visible from the unit.
Refer to local and national standards when loc-
ated outside of Europe.
Check the continuity of the protective current
circuit before the unit is used.
Check that the supply voltage corresponds
to the data on the machine plate of the unit,
, before connecting the unit to the
mains supply.
22
Summary of Contents for FlexPAK DX
Page 7: ...FlexPAK DX A E E A B C D G F 3A J I H 45 3B 7 ...
Page 8: ...FlexPAK DX 13 12 10 9 7 8 2 1 3 4 6 5 11 4A 11 7 8 9 12 13 15 14 17 16 10 18 4B 8 ...
Page 10: ...FlexPAK DX 6 A B 7 10 ...
Page 13: ...FlexPAK DX 11 12 13 14 13 ...
Page 14: ...FlexPAK DX A A A A C Min 2 1m 83 15 1 0 m 39 4 16 A B C 17 14 ...
Page 36: ...www nederman com ...