background image

FlexPAK DX

If the dust is abrasive, it may be necessary to use

thick-walled (or rubber-coated) material in bends and

other exposed areas.
To avoid pressure losses, the duct system is to be

as short as possible and designed with two or more

branches. Use larger diameters on the clean side to re-

duce pressure losses.

5.4 Installing the unit

WARNING! Risk of personal injury

Always stop the unit before looking into the

outlet. The fan rotates at high speed and debris

and particles coming out of the outlet may

cause eye injury.

For suppression units, detailed information re-

garding the installation of an explosion sup-

pression system can be found in the suppres-

sion system manual. Work is only to be carried

out by certified personnel.

To minimize any secondary explosion damage

and spread of fire, the proper documentation

and checklists of how to handle a fire in the

unit have to be developed. Such documents are

to be developed in co-operation with the local

fire authorities and take into account the prop-

erties of the collected material.

5.4.1 Indoor installation

CAUTION! Risk of equipment damage

If the exhaust air duct is blocked, the unit may

create an overpressure, that may cause major

damage to the heat exchanger.

Never completely seal a small room with the

unit installed.

Ensure that the room where the unit is in-

stalled is well ventilated.

It is recommended that the unit is positioned indoors.
Under some conditions, the unit may draw air directly

into the high-pressure fan. This may cause a dan-

gerous underpressure in the room if air cannot enter

freely. There are to be two openings for ventilation,

at least 250×250 mm (10"×10") in size. One is to be

placed up high and the other one down low.
The warm exhaust air is to be directed from the unit

and out of the premises, see 

Figure 9

, item 4. Connect

a duct that directs the exhaust air outdoors.
The air can be directed to a heat exchanger, but there

are not to be any dampers that may obstruct the air

flow.

5.4.2 Outdoor installation

If installed outdoors, consider the following:

• The area needs to be protected from the weather.

Cover the top of the unit to protect it from snow,

rain or falling debris.

• Install a lightning conductor, see 

Section 5.7 General

requirements

.

• Environmental and ambient conditions. See 

Sec-

tion 3.5 Technical data

.

5.4.3 Moving the unit

WARNING! Risk of personal injury

• Use proper lifting and protective equipment.
• Be careful not to let the unit tip over to avoid

a crushing risk.

• The unit is to be anchored to the floor, par-

ticularly if it is located at a high level, to en-

sure that it does not move and fall down. The

frame has four holes for anchoring. Take care

during relocation and transport of the unit to

avoid tipping. If the unit is to be moved, the

frame is to be attached to the front of the

bottom frame, see 

Figure 10

, item 1. Before

moving the unit ensure that it is emptied of

extracted materials.

5.5 Electrical installation

WARNING! Risk of electric shock

• Work with electric equipment is to be carried

out by a qualified electrician.

• The connected wiring system is to be elec-

trically connected to the Potential Equalizing

System (PES) on the premises.

The electrical connection is NOT to be

equipped with an earth leakage circuit breaker

when the frequency converter is provided with

an EMC filter. The EMC filter function will make

the earth leakage circuit breaker shut off the

power.

Following the European standard, the incom-

ing 3-phase supply is to be fitted with a hand-

operated disconnecting device that conforms

to the demands of disconnectors. The discon-

necting device is to be fitted within 2–3 m from

FlexPAK DX and be clearly visible from the unit.

Refer to local and national standards when loc-

ated outside of Europe.

Check the continuity of the protective current

circuit before the unit is used.

Check that the supply voltage corresponds

to the data on the machine plate of the unit,

see 

Figure 1

, before connecting the unit to the

mains supply.

22

Summary of Contents for FlexPAK DX

Page 1: ...Installation and service manual Compact dust collectors FlexPAK DX DX Models Original installation and service manual EN INSTALLATION AND SERVICE MANUAL 2021 07 07 144885 07 ...

Page 2: ...FlexPAK DX Trace back information Workspace Main version a2 Checked in 2021 07 07 Skribenta version 5 4 024 ...

Page 3: ...ries 20 5 Installation 20 5 1 Delivery check 21 5 2 Installation requirements 21 5 2 1 Bolts 21 5 3 Duct dimensions and installation 21 5 3 1 Requirements 21 5 3 2 Recommendations 21 5 4 Installing the unit 22 5 4 1 Indoor installation 22 5 4 2 Outdoor installation 22 5 4 3 Moving the unit 22 5 5 Electrical installation 22 5 6 Suppression system installation 23 5 7 General requirements 23 5 8 Auto...

Page 4: ...Loading new software 26 6 9 1 Frequency converter control panel 26 6 9 2 Firmware and software labelling 26 6 9 3 Upgrading the system 27 6 10 Spare Parts 27 6 10 1 Ordering spare parts 27 6 11 Recycling 27 6 11 1 Environmental information 27 7 Troubleshooting 28 7 1 Tools 28 7 2 Remove the lid of the start and control unit 28 8 Acronyms and abbreviations 30 9 Appendix A Installation protocol 32 1...

Page 5: ...s AB Ph Nederman Co SWEDEN Type Art no V Ser no Hz kW 50 A kW V A 60 Hz Year of manufacture hp 1 2116mm 83 3 772 mm 30 4 1670mm 65 8 1019 mm 40 1 58 mm 2 3 45 98 mm 90 88 90 98 98 98 98 98 220 320 540 640 O 14 18x 2A 5 ...

Page 6: ...FlexPAK DX 2116mm 83 3 1750mm 69 1650mm 65 0 120mm 4 8 80mm 3 25 1010mm 40 2B 2116mm 83 3 1114mm 43 9 1469mm 57 8 1670mm 65 7 508mm 20 0 2C 6 ...

Page 7: ...FlexPAK DX A E E A B C D G F 3A J I H 45 3B 7 ...

Page 8: ...FlexPAK DX 13 12 10 9 7 8 2 1 3 4 6 5 11 4A 11 7 8 9 12 13 15 14 17 16 10 18 4B 8 ...

Page 9: ...FlexPAK DX 20 21 19 Ø 151 mm Ø 195 mm 7 68 in Ø 220 mm 8 66 in 10 mm 39 in 8x Ø 5 94 in 22 5 4 5 7 x 5 mm 20 in 4C 1 2 3 6 7 8 9 16 15 14 13 11 10 12 4 5 5 9 ...

Page 10: ...FlexPAK DX 6 A B 7 10 ...

Page 11: ...FlexPAK DX EMERGENCY STOP SIEMENS LOGO 12 24RC XXXXXXX XXXXX XXXX ESC OK Stop Set Param Set Prg Name 6 1 5 4 2 3 8 11 ...

Page 12: ...FlexPAK DX 4 1 6 7 8 10 9 11 5 2 3 9 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 Ø13mm 1 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 Ø13mm 10 12 ...

Page 13: ...FlexPAK DX 11 12 13 14 13 ...

Page 14: ...FlexPAK DX A A A A C Min 2 1m 83 15 1 0 m 39 4 16 A B C 17 14 ...

Page 15: ...r personnel 3 Description 3 1 Function FlexPAK DX is a complete vacuum unit with a dir ect driven side channel fan fitted as one unit on a steel frame and a start and control unit with an integ rated 24 V transformer The unit is controlled by a fre quency converter has automatic start stop and auto matic filter cleaning 3 1 1 Filtration in two stages FlexPAK DX filters particles in two stages In t...

Page 16: ...ystem see Figure 2B Flameless venting see Figure 2C 3 3 1 Explosion venting The risk area may extend beyond the values given below The final risk area is to be evalu ated with regards to affecting factors found in Standard EN 14491 For assistance and information contact Neder man The harmful effects of an explosion are minimized by venting the pressure and flame of the explosion through an explosi...

Page 17: ...ased into the sur roundings and this must be taken into consideration when positioning the FlexPAK DX Please consult your local fire authority when determining suitable posi tioning of the FlexPAK DX with the flameless device Please refer to the installation and service or user manual for the flameless device supplied with the FlexPAK DX to find other limitations and information regarding safe use...

Page 18: ...mm 7 87 6 29 150 160 mm 7 87 6 29 Sound level 70 dB A 70 dB A Ambient temperature range 0 40 C 32 104 F 0 40 C 32 104 F Process air temperature 0 60 C 32 140 F 0 60 C 32 140 F Relative humidity Max 85 Max 85 Compressed air 6 7 bar 87 102 psi 6 7 bar 87 102 psi Material recycling 93 6 per weight 93 6 per weight Control filter area 1x12 m 1x129 sqft 1x12 m 1x129 sqft Control filter material Polyeste...

Page 19: ... filter see Fig ure 4A and Figure 4B 12 Cooling valve see Figure 4A and Figure 4B 13 High pressure side channel fan with pump char acteristic see Figure 4A and Figure 4B 14 PT100 sensor see Figure 4B 15 Outlet silencer after fan see Figure 4B 16 Control Filter and filter cartridge see Figure 4B 17 Pressure sensor see Figure 4B 18 Acoustic enclosure see Figure 4B 19 Cooling air hose from the freque...

Page 20: ...xPAK DX start and control unit is prepared for the connection of Nederman accessories and custom er connections The installation of accessories extra equipment and functions is described in the manual for each product and according to the electrical diagrams that came with the unit Consult your local Nederman represent ative for available accessories The most common accessory is a PS cable which a...

Page 21: ...e such as PVC is not to be used Almost all types of dust pick up stat ic electricity when sucked through a plastic pipe which significantly increases the risk for an explosion if the dust is combustible Do not collect material that may cause igni tion or blocking It is strictly prohibited to col lect material that may undergo dangerous chemical or thermal reactions and or self ig nite Some types o...

Page 22: ...ed to a heat exchanger but there are not to be any dampers that may obstruct the air flow 5 4 2 Outdoor installation If installed outdoors consider the following The area needs to be protected from the weather Cover the top of the unit to protect it from snow rain or falling debris Install a lightning conductor see Section 5 7 General requirements Environmental and ambient conditions See Sec tion ...

Page 23: ...h a protection device 5 8 Automatic bin emptying function See the PLC Settings Manual 5 9 Machining chips and swarf extrac tion See the PLC Settings Manual 5 10 Pneumatic filter cleaning valve See the PLC Settings Manual 5 11 ATEX Duct Isolation Valve See the PLC settings Manual 5 12 Ground check measurement All metal parts of the unit are to be grounded The system is to have two independent groun...

Page 24: ...tively in a com mon protective hose Air pressure hoses are to be anchored mechanically 6 Maintenance Read Chapter 3 Description before carrying out any maintenance work Maintenance work means that the equipment will have to be opened and possibly dis mantled This may constitute a risk and the mainten ance personnel need to know about the risks that may occur when acting incorrectly WARNING Explosi...

Page 25: ...ces Inspect the explosion venting panel and verify that it is intact 6 3 Empty the collector bin WARNING Risk of personal injury Ensure that there is no vacuum in the dust separator before removing the collector bin Crush hazard Be careful when lowering and refitting the collector bin Use proper pro tective equipment Wear goggles a dust mask and gloves when emptying the collector bin The plastic b...

Page 26: ...lean the motor compartment regularly The motor has 2 ball bearings The bearings are to be replaced after approximately 15 000 hours of opera tion If the ambient temperature often reaches 35 C 95 F the time between replacements is to be re duced In any case the bearings are to be replaced every fifth year The bearings are a standard type Contact Nederman or an authorized Nederman distributor for re...

Page 27: ...rts See also w w w n e d e r m a n c o m 6 10 1 Ordering spare parts When ordering spare parts always state the following The part number and control number see the product identification plate Detail number and name of the spare part see w w w n e d e r m a n c o m e n s e r v i c e s p a r e p a r t s e a r c h Quantity of the parts required 6 11 Recycling The product has been designed for compo...

Page 28: ...circuited If the PS cable is damaged press the Standby Running but ton to put the unit into Off mode and investigate the fault If necessary loosen the PS cable from the control unit see the electrical diagrams and use an ohmmeter across the leads in turn to locate the fault Defect PT100 tem perature sensor Check whether the PT100 sensor is defective as follows 1 Disconnect the PT100 sensor wire fr...

Page 29: ...l have to replace the pressure sensor Deposits or blockage in ducts on the way to the unit Clean the ducts Check the transport velocity The duct system is not properly dimensioned Re dimension the duct system or add an extra suction source Valves in the duct system are not working Check the duct system valves Low vacuum or air flow The filter cleaning does not work or is insufficient Check the fun...

Page 30: ...act your nearest authorized distributor or Nederman for technical advice Filter cleaning does not work The cleaning interval is too short Extend the cleaning interval Compressed air Pr t is 1 bar See Section 3 5 Technical data Too low compressed air pressure can result in premature filter clogging If the pres sure is lacking or too low the piston cannot open the FCV and lid properly This results i...

Page 31: ...ressure Sensor Filter Cleaning MFDPS Wr Main Filter Differential Pressure Sensor Warning MI Maintenance interval OT Operating total PE Protective earth PLC Programmable logic controller PS Pilot signal PSIFC Pilot signal interlock filter cleaning PTC Positive temperature coefficient PES Potential equalization system PVC Polyvinyl chloride RPS Relief Panel Sensor SLV Solenoid lower valve SSR Start ...

Page 32: ...ckets Unit No Date Performed by Control items Result Application requirements limits Material chemical thermal reaction risk Radiation heat from surroundings Delivery checks Missing components Transport damage Before installation Foundation Total weight product accessories and collected material Anchor bolts Access for maintenance filter replacement 1 m above the unit Mounting check availability M...

Page 33: ...air valve Compressed air connected to the unit Ground check measurement Check Incoming duct Incoming mains ground GND1 External mains ground Accessories if applicable Signs and warnings Intended use marked or indicated Safe bag replacement described or indicated Initial start up function test Maintenance switch Motor the direction of rotation Automatic filter cleaning Manual filter cleaning Cover ...

Page 34: ...sult Result Result Manual Nut VV Previous service record Inspect clean outside the unit Remove dust deposits clean work area Remove corrosion by grinding apply primer and touch up paint Vacuum measure negative pressure Cooling valve Motor bearings Fan Cooling fan motor Bearing motor fan Safety switch Box housing Main switch Cable harness Electrical connection points Ground earth connection Indicat...

Page 35: ...ng valve check Filter bags visual check Filter bags check pressure drop perform ance The main filter replace Clean and dry air check Ground measurement check GND1 Fan Incoming duct Incoming mains ground GND1 External mains ground Gaskets check for leakage and replace if necessary Plastic bag replace Bearings motor replace Bearings fan replace Check that the ventilation of the room is clear if plac...

Page 36: ...www nederman com ...

Reviews: