background image

FlexPAK

7 Troubleshooting

For information on fuses, see 

Section 3.4 Fuses

 and the included electrical diagrams.

There is no overcurrent relay. The frequency converter parameter for maximum current is adjusted from the
factory and is not to be adjusted.

If a fault occurs which cannot be adjusted according to the following descriptions, a Nederman service techni-
cian is to be called.

7.1 Tools

To carry out troubleshooting, it is necessary to have a multimeter with V DC and ohm measuring capabilities.

7.2 Remove the lid of the start and control unit

Remove the lid as follows:
1

Unscrew the four plastics screws in the corner of the control cabinet.

2

Lift of the lid.

3

Identify the PLC and the terminals at the bottom of the cabinet.

7.3 Troubleshooting guide

Error

Possible cause

Solution

The unit unexpec-
tedly goes directly
into Running mode
when the Standby/
Running button is
pressed.

• A valve at a workstation is open

and its micro switch is activated

• The PS cable is damaged with

its wires short-circuited

If the PS cable is damaged, press the Standby/Running but-
ton to put the unit into Off mode and investigate the fault.
If necessary, loosen the PS cable from the control unit, see
the electrical diagrams, and use an ohmmeter across the
leads in turn to locate the fault.

Defect PT100 tem-
perature sensor.

Check whether the PT100 sensor is defective as follows:

1

Disconnect the PT100 sensor wire from terminal 77
and measure the resistance between terminal 78 and
the disconnected sensor wire.

2

Measure the resistance in the sensor using an ohm-
meter. The values in the table below are standard val-
ues, so a deviation from the measured value is normal.
If the averaged output (in ohm) deviates more than
±2% from these values, the sensor will need to be re-
placed.

Temperature (°C)

Averaged output (ohm)

0

100

20

110

80

131

135

150

If the sensor has a resistance >150 ohms, there will be a
high-temperature alarm. To check whether the sensor in-
put is working correctly, disconnect the PT100 wire at ter-
minal 77 and connect a jumper between terminals 77 and
78. Press the OK button on the PLC to reset the alert.

If the alert disappears, the PT100 sensor input is working,
and the PT100 sensor will need to be replaced.

25

Summary of Contents for FlexPAK Standard

Page 1: ...Installation and Service Manual Compact dust collectors FlexPAK Standard Models Original installation and service manual EN INSTALLATION AND SERVICE MANUAL 2022 10 28 144838 07...

Page 2: ...FlexPAK Trace back information Workspace Main version a68 Checked in 2022 10 28 Skribenta version 5 5 022...

Page 3: ...2 Outdoor installation 20 5 4 3 Moving the unit 20 5 5 Electrical installation 20 5 6 General requirements 20 5 7 Ground check measurement 20 5 8 Automatic bin emptying function 21 5 9 Machining chips...

Page 4: ...f the start and control unit 25 7 3 Troubleshooting guide 25 8 Spare Parts 27 8 1 Ordering spare parts 27 9 Recycling 27 9 1 Environmental information 27 10 Acronyms and abbreviations 28 11 Appendix A...

Page 5: ...FlexPAK Figures AB Ph Nederman Co SWEDEN Type Art no V Ser no Hz kW 50 A kW V A 60 Hz Year of manufacture hp 1 907mm 35 7 966mm 38 0 2116mm 83 5 1670mm 66 0 EMERGENC Y S T O 2 5...

Page 6: ...FlexPAK 13 12 10 9 7 8 2 1 3 4 6 5 11 3 11 7 8 9 12 13 15 14 18 19 10 17 4 16 15 20 5 6...

Page 7: ...FlexPAK 6 1 2 3 6 7 8 9 16 15 14 13 11 10 12 4 5 7 7...

Page 8: ...FlexPAK EMERGENCY STOP SIEMENS LOGO 12 24RC XXXXXXX XXXXX XXXX ESC OK Stop Set Param Set Prg Name 6 1 5 4 2 3 8 8...

Page 9: ...FlexPAK 2 1 4 5 6 8 7 9 3 9 1 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 13mm 10 9...

Page 10: ...FlexPAK 11 12 13 14 10...

Page 11: ...FlexPAK 15 A B 16 11...

Page 12: ...FlexPAK A B C 4x 17 8x 18 12...

Page 13: ...FlexPAK A 4x B 19 Min 2 1m 83 20 1 0m 39 4 21 13...

Page 14: ...FlexPAK A B C 22 23 14...

Page 15: ...indicate a potential hazard to the health and safety of personnel and how that hazard may be avoided CAUTION Risk of equipment damage Cautions indicate a potential hazard to the product but not to pe...

Page 16: ...cording to EN 60335 2 69 Weight 439 kg 968 lb 439 kg 968 lb Inlet outlet diameter 150 160 mm 7 87 6 29 150 160 mm 7 87 6 29 Sound level 70 dB A 70 dB A Ambient temperature range 0 40 C 32 104 F 0 40 C...

Page 17: ...15 Outlet silencer after fan see Figure 4 and Fig ure 5 16 Cooling air hose from the frequency converter cabinet see Figure 5 17 Inlet silencer before the fan see Figure 4 18 Pressure sensor see Figu...

Page 18: ...d according to the electrical diagrams that came with the unit Consult your local Nederman represent ative for available accessories The most common accessory is a PS cable which al lows remote start...

Page 19: ...ions Transport velocity It is important to use the correct duct diameter to avoid pressure losses and dust deposits in the duct system Ensure that the correct transport velocity is achieved Correct ve...

Page 20: ...rth leakage circuit break er when the frequency converter is provided with an EMC filter The EMC filter function will make the earth leakage circuit breaker shut off the power Following the European s...

Page 21: ...ressed air line properly Connect a compressed air supply to the inlet see Fig ure 5 item 20 and Figure 9 items 6 and 7 Air pressure hoses are to be fitted together with electrical cables with straps a...

Page 22: ...rify the function of all emergency stop buttons alarms and signalling devices 6 2 Empty the collector bin WARNING Explosion risk Never use the unit without a bag WARNING Risk of personal injury Ensure...

Page 23: ...of the unit 12 Assemble the unit in reversed order 6 5 Check the filter cleaning function WARNING Risk of personal injury Crush hazard Pay attention when the com pressed air pressure cylinder and val...

Page 24: ...a label taped to the front of the PLC LOGO 8 soft ware is updated using an SD Card Follow the included instructions when the software needs to be updated To find the firmware and software revision num...

Page 25: ...ited If the PS cable is damaged press the Standby Running but ton to put the unit into Off mode and investigate the fault If necessary loosen the PS cable from the control unit see the electrical diag...

Page 26: ...n the system To check whether the sensor input is working disconnect the pressure sensor wire at terminal 2 and connect a jump er between terminals 2 and 1 Press the OK button on the PLC to reset the...

Page 27: ...ficient cleaning and premature filter clogging The CAS is connected to terminals X1 15 and X1 16 If no CAS is installed a jumper is linking the terminals to ensure that the CAS message is not displaye...

Page 28: ...memory FC Filter cleaning FCR Filter cleaning relay FCV Filter cleaning valve MFDPS Main Filter Differential Pressure Sensor MFDPS FC Main Filter Differential Pressure Sensor Filter Cleaning MFDPS Wr...

Page 29: ...FlexPAK SUV Solenoid upper valve TVFD Twin valve feed out device 29...

Page 30: ...kets Unit No Date Performed by Control items Result Application requirements limits Material chemical thermal reaction risk Radiation heat from surroundings Delivery checks Missing components Transpor...

Page 31: ...ir Compressed air valve Compressed air connected to the unit Incoming duct Incoming mains ground Accessories if applicable Signs and warnings Intended use marked or indicated Safe bag replacement desc...

Page 32: ...sult Result Result Previous service record Inspect clean outside the unit Remove dust deposits clean work area Remove corrosion by grinding apply primer and touch up paint Vacuum measure negative pres...

Page 33: ...aning valve check Filter bags visual check Filter bags check pressure drop perform ance The main filter replace Clean and dry air check GND1 Fan Incoming duct Incoming mains ground GND1 External mains...

Page 34: ...www nederman com...

Reviews: