FlexPAK
3.3.8 Alarm! Control Filter Clogged
The control filter is clogged and needs to be cleaned. It generally indicates a problem with the main filter, or the
control filter has been used too long and needs to be replaced. This alarm is activated when CFDPS-Al has been
activated for 5 seconds. Press the OK button to reset the alarm. See
ESC
OK
Alarm!
Control Filter
Clogged
Th 15:01
Unit is Stopped
Reset OK
à
3.3.9 TVFD Alarm! Upper Slide Not Closed
The TVFD Upper Solenoid Valve does not close while the dust bin is being emptied. TVFDC-Al has expired. It can
be caused by the following:
• The upper slide valve has not been activated as it should.
• Something can be stuck in the upper slide valve.
• The compressed air pressure hose has either been disconnected or the compressed air pressure is too low.
This message is only shown when TVFD advanced is activated.
ESC
OK
TVFD Alarm!
Lower slide
not closed
Th 11:23
Unit is Stopped
Reset OK==>
3.3.10 TVFD Alarm! Upper Slide Not Open
The TVFD Upper Solenoid Valve does not open while the dust bin is being emptied. TVFDO-Al has expired. It can
be caused by the following:
• The upper slide valve has not been activated as it should.
• Something can be stuck in the upper slide valve.
• The compressed air pressure hose has either been disconnected or the compressed air pressure is too low.
This message is only shown when TVFD advanced is activated.
ESC
OK
TVFD Alarm!
Upper slide
not open
Th 11:23
Unit is Stopped
Reset OK==>
21
Summary of Contents for FlexPAK
Page 7: ...FlexPAK 2 7 ...
Page 54: ...FlexPAK PLC setting Default value Customer specific value 54 ...
Page 55: ...www nederman com ...