FlexPAK
4.2.24 FlushTmp
Menu for temperature settings for regulating the fan’s outgoing air with the help of the flush valve (SFV1).
When the air temperature of outgoing air reaches the value set by FlushTMP, the flush valve (SFV1) opens to let
in the air in the system to reduce the outgoing air’s temperature.
Note that when the valve is open, the vacuum level from the workstations pipes leading to the main pipe can be
reduced. However, the flow in the main pipe partially increases flushing out dirt and debris.
The default settings for FlushTmp; FlushTmp is not activated:
ESC
OK
FlushTmp
1/1
On = 110
Off = 97
A
= 0,25
B
= -50
C
= -50
On=110: The temperature limit that is set to open flushing valve 1 (SFV1).
The default setting is 110°C (230ºF).
Off= 97 (207ºF): The temperature limit that is set to close the flush valve.
The default setting is 97°C (207ºF).
Ax=00:00: The current temperature of air exiting the system.
To activate FlushTmp, use the following settings:
ESC
OK
FlushTmp
1/1
On = 99
Off = 97
A
= 0,25
B
= -50
C
= -50
On=99: The temperature limit that is set to open flushing valve 1 (SFV1).
The default setting is 110°C (230ºF).
Off=97: (207ºF): The temperature limit that is set to close the flush valve.
The default setting is 97°C (207ºF).
Ax=00:00: The current temperature of air exiting the system.
4.2.25 CoolTmp
Menu for setting CoolTmp. See
The default settings for CoolTmp:
ESC
OK
CoolTmp
1/1
On = 97
Off = 96
On=97: The default temperature limit that is set to open Cleaning Valve V1
“SCV”. The default setting is 97°C (207ºF).
Off= 96: This parameter is set to (CoolTmp On -1), The default setting is
96°C (205ºF). Always set Off to On minus 1°C (On = 97-1 = 96).
Ax=00:00: The current temperature of air exiting the system.
4.2.26 TVFD-Al-Tmr
Menu for setting the maximum closing and opening times for both the upper and lower TVFD slides. If the upper
or lower TVFD slides do not close or open within the set time, an alarm is activated. This message is only used
when TVFD advanced is activated. See:
•
Section 3.3.9 TVFD Alarm! Upper Slide Not Closed
•
Section 3.3.10 TVFD Alarm! Upper Slide Not Open
•
Section 3.3.11 TVFD Alarm! Lower Slide Not Closed
•
Section 3.3.12 TVFD Alarm! Lower Slide Not Open
ESC
OK
TVFD-Al-Tmr
1/1
T
= 15:00s
Ta = 00:00s
T=15:00s: Maximum time for the upper and lower TVFD slides to close or
open. The default setting is 15 seconds.
Ta=00:00: The elapsed time since the closing or open cycle began.