L-PAK 150/250 Advanced
6.2.4 SSR_Time
Menu for setting the SSR timer. The SSR timer is for the amount of time before the unit goes from Idling mode to
Standby mode when the pilot signal disappears.
ESC
OK
SSR_Time
1/1
T
= 12:00m
Ta = 00:00
T = 12:00m: Time before SSR_Time is activated. The default setting is 12
minutes. The minimum setting is 5 minutes.
Ta = 00:00: The elapsed time since the pilot signal disappeared.
6.2.5 DIR_Time
Menu for setting the DIR timer. The DIR timer is the amount of time before the unit goes from Running mode in-
to Idling mode when the pilot signal disappears.
ESC
OK
DIRTmr
1/1
T
= 10:00s
Ta = 00:00
T = 10:00s: Time before DIR_Time is activated. The default setting is 10
seconds The minimum setting is 5 seconds.
Ta = 00:00: The elapsed time since the pilot signal disappeared.
6.2.6 Weekly timer
The weekly timer sets the unit to “Stand By” mode and “Off Mode” at preset times. If the pilot signal “PS” is act-
ive and the Vacuum unit is in Standby mode, the unit starts.
ESC
OK
NEDERMAN
Hi Vacum Unit
L-PAK
OFF
TimeTo Service
2000 Hours
ESC
OK
Thu
10:45
2018-02-01
ESC
OK
Stop
>
Program
>
Setup
>
Network
>
Diagnos!cs
>
ESC
OK
Set Parameter
Program Name
ESC
OK
H-Meter
>
ZV-Detect
>
SSR_Time
>
DIRTmr
>
WeekTmr
>
OTTmr
Z
ESC
OK
WeekTmr
1/2
D1
= MTWTF
On1
= 00:00
Off1
= -- --
D2
= MTWTF
On2
= -- --
ESC
OK
WeekTmr
2/2
Off2
= -- --
D3
= - - - - -SS
On3
= -- --
Off3
= -- --
Pulse
= Off
Do the following to set the weekly timer:
1
From the PLC status screen, press the down arrow to go to the date and time screen.
2
Press ‘Escape’ to go to the main menu.
3
Press the down arrow to go to ‘Program’. Press ‘OK’ to confirm.
4
Select ‘Set Parameter’. Press ‘OK’ to confirm.
5
Use the up or down arrows to find ‘WeekTmr’. Press ‘OK’ to confirm.
6
Use right, left, up and down arrows to select a value and change settings. Press ‘OK’ to confirm.
14