L-PAK 150/250 Standard

EN

14

6.2.3 

SSR_Time

Menu for setting the SSR timer. The SSR timer is for the amount of time before the unit 

goes from Idling mode to Standby mode when the pilot signal disappears.

ESC

OK

SSR_Time

1/1 

T = 12:00m

Ta  = 00:00

T = 12:00m: Time before SSR_Time is activated. The default setting is 12 

minutes. The minimum setting is 5 minutes.
Ta = 00:00: The elapsed time since the pilot signal disappeared.

6.2.4 

DIR_Time

Menu for setting the DIR timer. The DIR timer is the amount of time before the unit goes 

from Running mode into Idling mode when the pilot signal disappears.

ESC

OK

DIRTmr

1/1 

T = 10:00s

Ta  = 00:00

T = 10:00s: Time before DIR_Time is activated. The default setting is 10 

seconds The minimum setting is 5 seconds.
Ta = 00:00: The elapsed time since the pilot signal disappeared.

6.2.5 

FCTmr

Menu for activating and setting time between timer controlled filter cleaning.

ESC

OK

FCTmr

 

1/1 

Stat = ON

TH

= 01:00s

TL

= 60:00m

Stat =On Filter Cleaning timer activated Default is On.
TH=01:00s: Do not change the default setting of 1 second.
TL=60:00m: Time between automatic filter cleanings. The default setting 

is 60 minutes.
Ta=00:00: The elapsed time since the last automatic cleaning was 

activated. 

6.2.6 

Clean cycle 

Menu for setting the opening and closing times for the “FCV” Filter Cleaning Valve.
FCV cleaning cycle repeats X times depend on value of parameter ‘On’.
This function is always active when filter cleaning takes place. 

ESC

OK

Clean Cyc   

1/1 

Tch  = 05:00s

Tpu  = 01:00s

On  = 1

Cnt  =0

Tch = Vacuum Building time (Charge Time): Default is 5 seconds.
Tpu = Clean pulse time. Default 1 second.
On = Number of cleaning pulses.
Cnt = 0: Elapsed cleaning pulses.

NOTE! 

For the parameter ‘On’, the minimum value = 1.

NOTE! 

If On is set to 0, No filter cleaning is performed.

Time duration for a cleaning cycle below:

Example: 1 Cleaning pulse 

On=1, Tch=5, Tpu=1 → On * (Tch + Tpu) = 1*(5+1) =6s where Tch=05:00s and Tpu=01:00s.
The default time for a complete cleaning cycle is 6 seconds.

Summary of Contents for L-PAK Series

Page 1: ...L PAK Series L PAK 150 250 Standard 50Hz 60Hz 2130224 00 2018 09 13 Original PLC manual EN PLC MANUAL PLC Manual...

Page 2: ......

Page 3: ...L PAK 150 250 Standard 3 Figures 4 English 5...

Page 4: ...m ESC OK Hi Vacuum Unit Running Time 05 33 Min DIRTm 00 00 s OTTmr 00 00 h ESC OK Hi Vacuum Unit IDLING Time To StandBy T 05 33m PS PS ESC OK Hi Vacuum Unit Running Time 05 33 Min DIRTm 10 00 s OTTmr...

Page 5: ...1 5 Filter Cleaning 9 5 1 6 Status report 9 5 2 Warning messages 9 5 2 1 Time for service 10 5 2 2 Warning Fan Hi Temp 10 5 3 Alarm messages 10 5 3 1 Alarm Fan Hi Temp 11 5 3 2 Alarm Motor Protector...

Page 6: ...ocal Nederman representative immediately 2 Safety This document contains important information that is presented as either a warning caution or note See the following examples WARNING Risk of personal...

Page 7: ...f only one work station is in use and work stops at that one station the pilot signal stops If there is more than one work station connected to the unit and more than one work station is in use the pi...

Page 8: ...r Pilot Signal Mo 15 33 2018 01 22 5 1 3 Running Running mode The unit in Running mode The pump motor is on and the unit generates a vacuum The FCV is closed ESC OK Hi Vacuum Unit Running Time 05 33 M...

Page 9: ...en appears 1 Press Escape ESC and the up arrow at the same time to show the Status Report screen 2 Press Escape ESC and the up arrow at the same time to show the next Status Report screen Sn Software...

Page 10: ...vates a timer start which is shown in the display if the fan does not cool down when the timer elapses the vacuum unit will stop and the Alarm message Alarm Fan Hi Temp is activated ESC OK Warning Fan...

Page 11: ...Alarm Fan Hi Temp Vacuum Unit O Th 11 23 Reset OK Th The actual day and time when L Pak was stopped 5 3 2 Alarm Motor Protector Activated The motor is overheated Correct the problem and press OK OK to...

Page 12: ...3 Press the down arrow to go to Program Press OK OK to confirm 4 Select Set Parameter Press OK OK to confirm 5 Use the up or down arrows to find the parameter Press OK OK to confirm 6 Use the left and...

Page 13: ...confirm 5 Press the down arrow to go to Set Clock Press OK OK to confirm 6 Use the left and right arrows to move to cursor to parameter value Press OK OK to confirm 7 Use the up or down arrows to set...

Page 14: ...filter cleaning ESC OK FCTmr 1 1 Stat ON TH 01 00s TL 60 00m Stat On Filter Cleaning timer activated Default is On TH 01 00s Do not change the default setting of 1 second TL 60 00m Time between automa...

Page 15: ...4 Warning Alarm output Q4 Potential free output Terminal X1 33 34 When an alarm is activated Output Q4 and White lamp button on the control box side flash with interval 1 second on 1 second off Warnin...

Page 16: ......

Page 17: ...www nederman com...

Reviews: