The flashing error descriptions and patterns are described below:

LED shows

Description

Solution

1          Flashing

2          Flashing

3          Flashing

4          Off    

 

No project found on the 
control system or unable 
to start the project

o

  Try to upload the project again.

o

  Alternatively, there can be a problem in the project you have 

uploaded. In this case, try uploading an empty project and 
see if this works. 

1          Flashing

2          Flashing

3          Off

4          Off 

   

Unexpected Error

o

  Turn off the power to the control system for 20 sec before 

turning the power on again.

1          Off

2          Flashing

3          Flashing

4          Off

 

No contact to Neets 
extension unit

o  

Check to confirm that the serial number used in Project 
Designer matches the Neets extension unit.

o  

Check the network or RS-232 connection from the control 
system to the Neets extension unit.

1          Off

2          Flashing

3          Flashing

4          Flashing

 

Wrong firmware version in 
Neets extension unit

o  

The Neets extension unit has a different firmware than the 
one in the control system.

o  

Please upgrade the firmware by plugging in the USB cable 
from the Neets extension unit into a PC running Project 
Designer and follow the instructions.

1          Off

2          Off

3          Flashing

4          Off

 

Error in serial  
number

o  

You need to return the unit to Neets or your local dealer for 
replacement/repair.

1          Flashing

2          Off

3          Off

4          Flashing

 

Resuming factory default 
settings

o

  When pressing Switch 1 and 4 during power on, the system 

will delete the current settings and resume factory default. 
This method is only intended to be used if the control system 
locks up and enters “Unexpected Error”

   Off button flashing 

once per second 
(all buttons flash if 
no off button is 
configured)

Unable to connect to  
configured TCP device.

o  

 Verify the TCP device in the project is alive and responding on 
the specified IP.

   Off button flashing 

4 times per 
second  
(all buttons flash if 
no off button is 
configured)

Password incorrect on 
configured LAN device.

o  

 Verify that the password is entered correctly in Project 
Designer for all LAN devices that require password.

Summary of Contents for Control-UniForm

Page 1: ...Neets Control UniForm Installation Manual ...

Page 2: ...HANGES Neets reserve the right to change the specification and functions of this product without any notice Check www neets dk for the latest updated version of this manual Questions AFTER reading this manual can be addressed to your local distributor or Neets A S Denmark by E Mail Support Neets dk or you may use our contact form at www neets dk Revision list This document no 310 0350 002 has the ...

Page 3: ... components inside These openings must never be blocked by other objects Do not use this equipment near water To reduce the risk of fire or electric shock do not expose this apparatus to rain or moisture and objects filled with liquids Unplug the product before cleaning Clean only with a dry cloth and not cleaning fluid or aerosols Such products could enter the unit and cause damage fire or electr...

Page 4: ...Instructions 3 Contents 4 Description 5 Quick guide to the UniForm 6 Installation 7 Connections and Controls 7 User Interface 7 I O ports 8 RS 232 IR port 8 LAN port 9 Configuration through USB port 9 Troubleshooting 9 Error indication using LEDs 10 Specifications 11 ...

Page 5: ...e ready to begin UniForm is a perfect choice for the classroom meeting or conference room and is easy to install UniForm can control devices through RS232 and LAN Function description RS 232 Tx Rx or IR Tx controls up to 2 IR devices on the port 1 RS 232 Tx or IR controls up to 2 IR devices on each port 2 LAN device control 2 Power over Ethernet Yes I O 3 Buttons 8 USB port for programming 1 PIR s...

Page 6: ...ion 1 Push buttons for controlling the AV setup with LED status lights 2 Front cover with label for button description 3 Mini USB for programming Rear Number Description 1 1 x RS 232 port Bidirectional or IR Unidirectional 2 2 x RS 232 or IR ports Unidirectional 3 1 x RJ 45 Network LAN connector with PoE functionality 4 3 x Digital Input Output 1 1 2 3 1 2 3 4 ...

Page 7: ...r Interface E ink and buttons The front of the UniForm consists of an E ink display showing the functions related to the four bottuns on each side of the display The buttons are numbered as shown to the right Each button has a tactile click feedback to ensure proper activation Also each button has an embedded multicolor LED light to indicate current status of the AV system E ink display button fun...

Page 8: ...cted to ground in order to change state RS 232 IR ports The RS 232 ports TX 1 RX 1 TX 2 TX 3 are used for one or two way communication Port 1 is a two way port which can be used for devices for which a reply function is required such as a projector All of the RS 232 IR ports can be configured in the Neets Project Designer software either as RS 232 or as IR emitter Connect the port as shown below R...

Page 9: ...the Neets Project Designer software It can t be used to control any external devices The USB port is located on the surface facing the floor when hanging on the wall The host USB port can power the control system while configuring so no external power is needed when configuring the UniForm However PoE and the USB port may be connected at the same time for example when changing the configuration on...

Page 10: ...nsion unit has a different firmware than the one in the control system o Please upgrade the firmware by plugging in the USB cable from the Neets extension unit into a PC running Project Designer and follow the instructions 1 Off 2 Off 3 Flashing 4 Off Error in serial number o You need to return the unit to Neets or your local dealer for replacement repair 1 Flashing 2 Off 3 Off 4 Flashing Resuming...

Page 11: ...t trigger low 1VDC Input trigger high 4VDC Output type Open drain Isolated output No Max voltage load 24 VDC Max current 0 5 A Connector 4 pin screw block Network LAN Speed 10 100 Mbit Duplex modes Half or Full DHCP Default off Default IP 192 168 254 252 Default gateway 192 168 1 1 Default subnet mask 255 255 255 0 Power over Ethernet Compliance 802 3af 802 3at 802 3af mode A B PD Class 1 General ...

Reviews: