XR-YM – YOKE MOUNT INSTALLATION
Refer to alternate instructions if using Conduit, Hook, Pole
or Wall Mount
STEP 1.
Inspect shipping package and contents to ensure no damage has occurred
during shipping.
STEP 2.
Make wiring connections from branch circuit conductors to factory
provided lead wires using one of the 3/4" NPT threaded entries. Follow
wiring method requirements of the Canadian Electrical Code or National
Electrical Code for the specific hazardous location of the installation.
NOTE:
To aid in assembly and provide protection against ingress, use of a petrolatum or
soap thickened mineral oil based thread lubricant/sealant is necessary.
Un-used conduit opening must be plugged to maintain the integrity of the
enclosure.
STEP 3.
Loosely assemble Yoke mount with carriage bolts on inside and washers
and nuts on the outside.
NOTE:
Depending on which mounting hole is used in the curved slot, the luminaire may
be configured for an upward or downward adjustable swing.
STEP 4.
Thread installed wiring through openings in yoke mount cheek plate and
yoke mount bracket. Mount yoke assembly to luminaire using 4x M6 Socket
Head Cap Screws and Washers (Provided). Torque fasteners to 5 Nm (45
in-lbs).
STEP 5.
Mount luminaire assembly to desired location using 4x 1/4-20 OR M6
Screws or Bolts (Not Provided).
STEP 6.
Adjust and aim luminaire to desired position. Torque hardware nuts to 9
N-m (80 in-lbs).
STEP 7.
Resume installation instructions provided with luminaire. (STEP 4 in XR
Installation Instructions from the Surface/Ceiling Mount installation
provided with Luminaire).
Step 5
Step 3
This XR-YM kit is intended for use with UL Listed XR luminaire as
marked on the luminaire nameplate.
Accessory Package Contents
INSTALLATION STEPS
XR-YM
PART NAME
QTY
1
1
1
4
4
4
4
YOKE MOUNT A
YOKE MOUNT B
CHEEK PLATE
1/4-20 HEX NUT
1/4" FLAT WASHER
1/4-20 x 0.5in CARRIAGE BOLT
M6 x 25mm HEX HEAD CAP SCREW
TM
Nemalux
I N D U S T R I A L
XR-HAZ
rrev. A-13
8-14
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
MADE IN CANADA
WARNING:
The XR head must not face upwards
any degree beyond the horizontal
position for Class II, Division 2, Zone
22 and Class III hazardous location
installations.
ATTENTION:
Le luminaire XR ne doit pas être orienté
vers le haut à un degré quelconque au-
delà de la position horizontale pour les
installations en zones dangereuses de
classe II, division 2, zone 22 et classe III.
LIGHT
BEAM
HORIZON
WARNING