51
During blast chilling:
needle probe temperature reading is displayed
• LED
is on
parameter r4 defines end of chilling temperature
parameter r6 defines maximum chilling time
parameter r8 defines working setpoint
• press
several times:
- remaining chilling time is displayed
“nEg” is displayed
- displays chiller internal temperature which flashes
- escape this procedure or do not use for 15 seconds
If the temperature detected by the needle probe reaches end of chilling temperature
before maximum chilling time has been reached:
the chiller goes into storage mode
“End” is displayed
a buzzer is activated and buzzer time is defined by parameter AA
press a key to turn off the buzzer; press the key again to delete the prompt “End”.
If the temperature detected by the needle probe has not reached end of chilling
temperature before maximum chilling time has been reached:
blast chilling will continue
• LED
flashes and LED remains on
the buzzer is activated
• press
several times:
- to turn off the buzzer
- the extra chilling time elapsed over the maximum blast chilling time is displayed
- displays chiller internal temperature
“nEg” is displayed
- escape this procedure or do not use for 15 seconds
when the temperature reading detected by the needle probe reaches end of chilling
temperature:
- the chiller goes into storage mode
- LED
continues to flash and LED continues to remain on
- “End” is displayed
- a buzzer is activated and buzzer time is defined by parameter AA
- press a key to turn off the buzzer; press the key again to delete the prompt “End”.
During storage:
- chiller internal temperature is displayed
• if chilling results correct, LEDs
and remain on; if chilling results to be
incorrect, LEDs and are on and LED
flashes
parameter rA defines working setpoint
• press
several times: